Operation
4-5
Reset Panel
The reset panel looks like the figure below.
Reset Switch
The momentary pushbutton switch must be
pressed and held for 15 seconds after turning
on main power and after and emergency stop.
Figure 4. Reset Panel
Temperature Controls
Your laminator has heated rolls that allow you to laminate with thermal films and pressure sensitive films
that require heat to activate the adhesive. The temperature controls have a maximum temperature set at
the factory. The operator cannot set the temperature above this point. The controllers are also set up
with an over temp alarm. If there is a failure and the heater coils heat out of control, the temperature
controller will create an e-stop condition.
The temperature controller looks like the graphic shown at the left. The
operator only needs to press and hold the
asterisk
key then press the
up
arrow
key to raise the “Set Point Temperature” or the
down arrow
to lower the
“Set Point Temperature”. The square green LED in the upper left will stay on
initially as heater comes up to temperature and flash as the controller pulses
electricity to maintain the heat in the rolls. The top alarm LED will flash on if
the rolls exceed the upper temperature limit set at the factory and then the
machine will go into an E-stop condition. The rolls must be allowed to cool
down before restarting machine. The machine can be restarted by pressing
and holding the Reset button for 15 seconds. If the machine fails again in the
same manner, the laminator should be serviced by qualified personnel.