![Advanced Energy Thyro-PX Anybus Modbus TCP Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/advanced-energy/thyro-px-anybus-modbus-tcp/thyro-px-anybus-modbus-tcp_manual_2855934016.webp)
Table 11. Parameter list (Continued)
API
#
Read /
Write
Address
Parameter Name
Type
Parameter Description
Dec
Hex
44
Read
4198
1066
Device CPU temperature
r
FLOAT
CPU temperature - read
45
Read
4200
1068
Device error r
UINT32
Error - read
Bit 0: Aux. supply error
Bit 1: Parameter error
Bit 2: Frequency error
Bit 3: Internal communication error
Bit 4: Temperature CPU too high
Bit 8: Phase L1 missing
Bit 9: Phase L2 missing
Bit 10: Phase L3 missing
Bit 11: Fuse 1 broken
Bit 12: Fuse 2 broken
Bit 13: Fuse 3 broken
Bit 14: Thyristor 1 short-circuit
Bit 15: Thyristor 2 short-circuit
Bit 16: Thyristor 3 short-circuit
Bit 17: External error 1 (customer-
specific)
Bit 18: External error 2 (customer-
specific)
Bit 19: External error 3 (customer-
specific)
Bit 21: Extension card X53
configuration error
Bit 22: Extension card X54
configuration error
Bit 23: External extension 1
configuration error
Bit 24: External extension 2
configuration error
Bit 25: dASM card configuration error
Bit 26: Anybus configuration error
Bit 27: Internal error
Advanced Energy
®
Thyro-PX
™
Anybus
®
Modbus TCP
57010166-00A
Thyro-PX
™
Anybus
®
Modbus TCP
16