Table 11. Parameter list (Continued)
API
#
Read /
Write
Address
Parameter Name
Type
Parameter Description
Dec
Hex
36
Write
4182
1056
Flexible link 16 w
UINT32
FLOAT
Flexible link number 16 - write
37
Write
4184
1058
Flexible link 17 w
UINT32
FLOAT
Flexible link number 17 - write
38
Write
4186
105A
Flexible link 18 w
UINT32
FLOAT
Flexible link number 18 - write
39
Write
4188
105C
Flexible link 19 w
UINT32
FLOAT
Flexible link number 19 - write
40
Write
4190
105E
Flexible link 20 w
UINT32
FLOAT
Flexible link number 20 - write
41
Write
4192
1060
Device Commands w
UINT16
Device command - write
Bit 0: Clear energy counter power
controller #1
Bit 1: Clear energy counter power
controller #2
Bit 2: Clear energy counter power
controller #3
Bit 3: Regulator lock power controller
#1
Bit 4: Regulator lock power controller
#2
Bit 5: Regulator lock power controller
#3
Bit 6: Pulse lock power controller #1
Bit 7: Pulse lock power controller #2
Bit 8: Pulse lock power controller #3
Bit 9: External Error 1
Bit 10: External Error 2
Bit 11: External Error 3
Bit 12: Load parameters (from
EEPROM to Flash)
Bit 13: Save parameters (from Flash to
EEPROM)
Bit 14: Fault acknowledgement (Quit)
Bit 15: "Only if bit set" (special
function)
42
4194
1062
43
Read
4196
1064
Device operating hours r FLOAT
Operating hours - read
Advanced Energy
®
Thyro-PX
™
Anybus
®
Modbus TCP
57010166-00A
Thyro-PX
™
Anybus
®
Modbus TCP
15