6.3 Connection to the piping network
Using the sleeves or a fl exible hose section, connect the suction and discharge pipes from the system
to the vacuum unit.
Do not glue the hoses extremities to the vacuum unit’s joints.
The maximum gross length admitted between the point of fuel sampling and system is 30 m.
The calculation of net piping length is affected by:
- The type of fuel to be transported
- The quantity of curves in the tract where the fuel passes through
- The length of vertical tracts where the fuel passes through
The exhaust pipe (air expulsion from the unit) maximum length admitted is 5 m (single-pipe system)
The exhaust pipe of the air (from the unit) maximum length admitted, in case it returns to the point of fuel
sampling, is 10 m (double-pipe system)
See “installation data sheet” on our website
A
B
B
1. Put the closure cap (A) on the extremity of
the vacuuming joint which is not used for
the connection (B).
2. Connect the suction and the exhaust
hoses of the machine using the sleeves
or a tract of fl exible hose.
Exhaust
Vacuuming