Distance to flammable material
Behind the stove
Behind stove with
insulated flue pipe
To the sides of the
stove
To furniture
20 cm
12 cm
34/11 cm
120 cm
Please note: that the Aduro 15SK must be installed on a floor with the adequate load-bearing capacity. If the
existing construction does not meet this requirement, appropriate adaptation measures must be taken (e.g. a load-
distributing plate).
If the wood burning stove is to be placed close to flammable material, such as a wooden floor or carpet, it must be
placed on a non-flammable base. The floor plate should extend for at least 30 cm in front of the wood burning
stove, and 15 cm on each side
– measured from the combustion chamber opening.
3.2 Pipe connection
Aduro 15SK leaves the factory with the flue outlet mounted on the top. If you require the flue outlet on the back,
remove the round circle from the rear cover and heat shield at the upper rear of the stove and then exchange the
exhaust connector (located on the top outlet above the stove) with the cover plate (that covers the rear outlet). The
top outlet is finished with the plate that lies in the ash drawer. A flue pipe with an internal diameter of 150 mm
should be used for Aduro stoves.