Total Access 1248 Quad T1 IMA 48-Port DSLAM with Modem Installation and Maintenance Practice
6-2
61179641AL1-5C
To remove a fan module, perform the following steps:
1. Loosen the screw that holds the fan module in place.
2. Remove the fan module by pulling it straight out of the chassis.
To install a new fan module, perform the following steps:
1. Insert the new fan module by pushing it straight into the chassis.
2. Tighten the screw that holds the fan module in place.
Fan Filters
The Total Access 1248 Expansion DSLAM fan module comes with a single fan filter. The filter
is designed to remove particles from the air before it is pushed through the system.
Replacement filters are available from ADTRAN. This filter should be inspected at least every
90 days and replaced as necessary.
To replace a filter, remove the fan module, remove the old filter material and tuck the new
filter in, ensuring that the edges of the filter are behind the metal tabs provided to hold the
filter (see
).
SNMP/TFTP AND TL1 CONFIGURATION STORAGE AND RETRIEVAL
Use the following SNMP/TFTP and TL1 commands to store or retrieve the Total Access 1248
System Configuration Archive (SCA) file.
NOTE
In some installations, the configuration file can be stored and
retrieved in one operation for multiple Total Access 1248 systems.
This is accomplished by incorporating the SNMP/TFTP or TL1 com-
mands into scripts.
SNMP / TFTP
These objects are located in the ADTRAN-TA1200Shelf-MIB.mib, under adTA1200ShelfProv.
Save
Set TFTP Server IP address with
adTA1200SCATftpServerHostName
Set filename using
adTA1200SCAFileName
Initiate transfer using
adTA1200SCAInitiateSave
(option initiate (1))
Restore
Set TFTP Server IP address with
adTA1200SCATftpServerHostName
Set filename using
adTA1200SCAFileName
Initiate transfer using
adTA1200SCAInitiateRestore
(option initiate (1))