FUNCTION DESCRIPTION 

 

 Display & Functions   

 

Max / Mini recording: 

 

 

The meter will storage the maximum and minimum value in 

[ user level] 

during power on in order to review drifting of PV. 

 

Display functions:

 

 

(Please refer to step A-07)

 

PV / Max(Mini) Hold / RS 485 programmable in 

[

dsply

function of 

[

input group

]

 

 

Present Value

  pv

:

  The display will show the value that Relative to Input signal. 

 

Maximum Hold

 

maXhd

 / Minimum Hold

 

miNhd

 :

 

 

 

 

 

 

 

 

 

 

 

The meter will keep display in maximum(minimum) value 
during power on, until manual reset by front key in

 

[User 

level]

, rear terminal is close 

[

External Control Input(

ECI

)

 ] 

or press front down or up key to reset (according to setting, 
please refer to the function of the ECI Group)

 

 

 

     

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 

Default Input:

[

lOsc

]: 

  )00

hIsc

]: 

19(99

Digital fine adjustment:   

input 2.75mV, 

[

pVzro

]

set to be 

 8)00

        

input 9.00mV, 

[

pVspn

]

set to be 

17)00

Display: Low point from 55.00 to 80.00 
        High point from 180.00 to 170.00

 

SCALE

INPUT

0V

10.0mV 

5.0mV 

2.75mV 

9.00mV 

19(99

[

h Isc

]

[

l Osc

]

)00

10)00

18)00

5%00

8)00

17)00

Excit. Pw.
10Vdc 
Sensor 
1.0mV/V

 

 

 

 

 

 

X

 

Please find the 

 

  M.H 

sticker that enclosure the package 

of the meter to stick on the right side of square orange LED 

 

 

 

 

 

 Reading Stable Function 

 

 

 

Average display:

 

 

 

 

 

 

 

 

 

 

 

 

Max. ( Mini.) Hold & Reset 

 

                                           

 

 

 

 

 
 

 

 
 

 

 

 

 
 

 

 

Reset the Max 

(M ini) H old by 

EC I or F. Key

 

O
N

Level 

Trigger 

Maxim um   Hold 

Present 

Value 

 

 

Jittery Display caused by the noise or unstable signal. User can set the times to average 
the readings, and to get smoothly display. 
The meter’s sampling is 15cycle/sec. If the 

[

 avg

]

(Average) set to be 

    3

 to 

express the display update with 5 times/sec. The meter will calculate the sampling 1-3 
and update the display value. At meantime, the sampling 4-6 will be processed to 
calculate.

Remote Display by RS485 command

 

rs485

 :

 

 

 

 

 

 

 

 

 

 

 

 

The meter will show the value that received from RS485 
sending. In past, The meter normally receive 4~20mA or 0~10V 
from AO or digital output from BCD module of PLC. We support 
a new solution that PV shows the value from RS485 command 
of master can so that can be 

save cost and wiring

 from PLC.

 

 

Other functions

 :

 

 

Average set to be 3 

                                           

 

 

 
 
 
 
 
 
 
 

…….

Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 

…….

Display Update Value =   
(Sample 1 + Sample 2 + Sample 3)/3

Display Update Value =   
(Sample 4 + Sample 5 + Sample 6)/3

 

Remark:

 The higher average setting will cause the response time of 
Relay and Analogue output slower.

 

 

 

Moving average:

 

 

 

The meter is also support relative PV (

PV) and PV hold 

functions that set in 

[

  eci group

].

 Please refer to 

explain of ECI functions. 

 

Low cut:

 

Settable range from -19999~+99999 counts.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jittery Display caused by the reasons as like as noise or unstable signal. User can set 

the times to average the readings, and get smoothly display. 
The meter’s sampling is 15cycle/sec. If the 

Mavg

]

(Moving Average) set to be 

    3

 

expressed the display update with 15 times/sec.,   

In the first updated display value will be same as average function. In the next updated 

display value, the function will get the new fourth sample (sample 4) then throw away the 
first sample (sample 1) that the newest 3 samples(sample 2,3,4) will be calculated for the 
updated display value. 

 

The users can set the value range. 
1.

 

If set the positive value (X1) here to display "0" which it 
expressed to be low-cut the PV between "+X1 (plus)" & 
"-X1(minus)" /absolute value 

PV< l Setting value (X1) l, the display will be shown 0 

EX: Low Cut is set for 0.50. If the display is from 

-0.50~+0.50, that will be 0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Cut set to be +0.50 

                                           

 

 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 

 

Low Cut is set for 0.50, if the PV is 

from -0.50~+0.50, that display will be 0.

 

PV according 

to input signal 

Present 

Value 

Low cut 

function 

0.50 

-0.50 

)50 

[

 lOcut

]

X1

 

X1

 

 

 

 

 

 

 

Moving Average set to be 3 

                                           

 

 

 
 

 
 
 

 
 
 
 

 
 
 

 

 

 
 
 

 
 
 
 

 

Sample 1 Sample 2 Sample 3 Sample 4 Sample 5 Sample 6 

……. 

In first 3 samples, Display Update Value 
= (Sample 1 + Sample 2 + Sample 3)/3 

Display Update Value   

= (Sample 2 + Sample 3 + Sample 4)/3 

Display Update Value   
= (Sample 3 + Sample 4 + Sample 5)/3

Display Update Value   
= (Sample 4 + Sample 5 + Sample 6)/3

……. 

 

Remark:

 The higher moving average setting wouldn’t cause the 

response time of Relay and Analogue output slower after first 3 
samples.

 

 

 

Digital Filter:

 

The digital filter can reduce the magnetic noise in field. 

 

 

 

 

 

2.

 

If set the negative value (X2) here to display "X2"    which it 
expressed to be low-cut the PV that it's under the X2 setting 
value; 

PV< Setting value(X2), the display will be shown X2. 

EX: Low Cut is set for -0.01. If the display is < -0.01, and all 

the display will be -0.01. 

 

 

 

 

 

 

 

The digital filter can reduce the influence of spark noise caused by 
magnetic of coil. 
If the values of samples are over digital filter band (fix in firmware and about 
5% of stable reading) 3 times (Digital Filter set to be 3) continuously, the 
meter will admit the samples and update the new reading. Otherwise, it 
will be as treat as a noise and skip the samples. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Cut set to be -0.10 

                                           

 

 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 

 

-0.10 

Low cut 

function 

Low Cut is set for -0.10, if the PV is 

under (< = -0.10), that display will be -0.10.

 

Present 

Value 

PV according 

to input signal 

-)10 

[

 lOcut

]

 

X2

 

 

 

 

 

Digital fine adjust:

 

Settable range: -19999~+29999 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Users can get Fine Adjustment for Zero & Span of PV by front key of the 
meter, and “

Just Key In

” the value which user want to show in the 

current input signals. 
Especially, the 

[

pVzro

[

pVspn

are not only in zero & span of PV, but 

also any lower point for 

[

pVzro

& higher point for 

[

pVspn

]

. The meter 

will be linearization for full scale. 

 

 

 

 

 

CS2-

V

CSM-321S CSM-

CSM-

CS2-T 

CSM-321S CSM-

CSM-

CSM-321S 

CSM-

CSM-321S 

Содержание CS2-T

Страница 1: ...1M ohm Set points Four set points S1 Type S 400 1600 C 1M ohm Control relay Four relays B1 Type B 400 1800 C 1M ohm Relay 2 Relay 3 Dual FORM C 5A 230Vac 10A 115V Relay 1 Relay 4 Dual FORM A 1A 230Va...

Страница 2: ...FN C PANEL CUT OUT 92 0 2 W x 44 0 2 H mm EMC EN 55011 2002 EN 61326 2003 Safety LVD EN 61010 1 2001 CONNECTION DIAGRAM Environmental Operating temp 0 60 C Operating humidity 20 95 RH Non condensing T...

Страница 3: ...as noise or unstable signal User can set the times to average the readings and get smoothly display The meter s sampling is 15cycle sec If the Mavg Moving Average set to be 3 expressed the display up...

Страница 4: ...ading will show the differential value The relay energized with latched function is for electrical safety and human protection For example a current meter relay installed for the over current alarm of...

Страница 5: ...Lo alarm Hi Lo energized hold Go function DO function RL 1 RL2 RL3 RL4 COM ECI1 ECI2 ECI3 ENT FN Kg cm2 R L 1 RL 2 RL3 RL4 COM ECI1 ECI2 ECI3 ENT FN Kg cm2 Analogue output option Remote Display Please...

Страница 6: ...x Mini Hold indication 2 square orange LEDs CO M H displayed When the display function has been selected in Maximum or Minimum Hold function Stickers Each meter has a sticker what are functions and en...

Страница 7: ...4 20 A 2 0 lOsc lOsc Low scale of PV Don t set B 2 0 0 rYsd rYsd Start delay time for Relay energized 0 00 0 9 M 59 9 S C 2 pVhld ecI2 ecI2 External Control Input 2 none reLpv pVhld Mrst rYrst di D 2...

Страница 8: ...hld hIhld do E 1 1 adres adres Device number of the meter 1 255 A 12 0 Pcode Pcode Pass Code for enter Engineer Level 0000 9999 B 12 0 ry hy ry hy Relay 3 Hysteresis 0 5000 counts E 2 9600 baud baud B...

Отзывы: