ADTEK CS2-T Скачать руководство пользователя страница 2

CS2-T-2010-09-27

 

C2-09

-2/8 

 

 

 

 

 

 Analogue output(option) 

 

 

Accuracy: 

±

 0.1% of F.S.; 16 bits DA converter   

 

„

 

DIMENSIONS 

Ripple:

 

±

 

0.1% of F.S. 

 

Response time:

 

100 m-sec. (10~90% of input) 

 

Isolation: 

AC 2.0 KV between input and output 

 

Output range: 

Specify either Voltage or Current output in ordering 

 

 

Voltage:

 0~5V / 0~10V / 1~5V programmable

 

 

 

Current:

 0~10mA / 0~20mA / 4~20mA programmable

 

 

Output capability: 

Voltage: 0~10V: 

 1000

 

 

Current: 4(0)~20mA: 

 600

 max

 

 

Functions: 

aOhs

(output range high): Settable range: -19999~29999   

 

 

aOls

(output range Low): Settable range: -19999~29999 

 

 

aOlmt

 (output High Limit): 0.00~110.00% of output High 

 

Digital fine adjust:

 

aOzro

Settable range: -38011~+27524

 

 

 

aOspn

Settable range: -38011~+27524

 

 

 

92.0

+0.2

44.0

+0.2

PANEL CUT-OUT 

96.0

48.0

FRONT VIEW 

 

Unit: mm

8.0

 

12.0

100.0

 

Dimensions: 96mm x 48mm x 120mm 

Panel Cutout: 93mm x 45mm (advise) 

 

 

 

 

 

  RS 485 Communication(option) 

 

 

Protocol: 

Modbus RTU mode 

 

„

 

INSTALLATION 

Baud rate: 

1200/2400/4800/9600/19200/38400 programmable 

 

Data bits: 

8 bits   

 

The meter should be installed in a location that 

does

 not exceed the 

maximum operating temperature and provides good air circulation.

 

Parity: 

Even, odd or none (with 1 or 2 stop bit) programmable

 

 

Address: 

1 ~ 255 programmable 

 

Remote display: 

to show the value from RS485 command of master

 

 

Distance: 

1200M 

 

Terminate resistor: 

150

 at last unit. 

 

 

 

 

 Electrical Safety   

 

 

Dielectric strength:

 

AC 2.0 KV for 1 min, Between Power / Input / Output / Case 

 

Insulation resistance:

 

100M ohm at 500Vdc, Between Power / Input / Output 

 

Isolation:

 

Between Power / Input / Relay / Analogue / RS485 / E.C.I. 

 

   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1.0~8.0 mm 

FIX HOLDER:

104 mm(L) / W M3

 

 

 

R

RL

R

R

COM 

 

C

C

C

 

ENT/FN

 

 

?  

 

?

 

?

°C

PANEL CUT-OUT:

92

+0.2

(W) x 44

+0.2

(H) mm

EMC:

 

EN 55011:2002; EN 61326:2003 

 

Safety(LVD):

 

EN 61010-1:2001 

 

„

 

CONNECTION DIAGRAM 

 

 

 

 Environmental  

 

 

Operating temp.:

 

0~60 

˚

 

Operating humidity:

 

20~95 %RH, Non-condensing 

 

Temp. coefficient:

 

100 PPM/

˚

 

Storage temp.:

 

-10~70 

˚

 

Enclosure:

 

Front panel: IEC 549 (IP54); Housing: IP20 

 

 

 

 

 Mechanical   

 

 

Dimensions:

 

96mm(W) x 48mm(H) x 120mm(D) 

 

Panel cutout:

 

92mm(W) x 44mm(H) 

 

Case material:

 

ABS fire-resistance (UL 94V-0) 

 

Mounting:

 

Panel flush mounting 

 

Terminal block: 

Plastic NYLON 66 (UL 94V-0) 

 

 

10A 300Vac, M2.6, 1.3~2.0mm

2

(16~

2

2AWG) 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

21 22

24 25

23

27 28

26

29 30 31 

33 

32 

34 

Relay 3 

Relay 2   

Relay 1 

Relay 4 

Analogue

output 

A  B 

RS 485 

port 

ECI1

ECI3 COM 

ECI2

External Control Input 

FG 

1  2 

4  5 

7  8  9  10 

11  12 

14  15 

13 

 

Terminal blocks: 

10A/300Vac, M2.6, 

M2.6, 1.3~2.0mm

(16~

2

2AWG) 

AC

 

86~265V 

DC 100~300V 
DC 20~56V

 

AC230V 

AUX. POWER 

AC115V 

ADH

 

ADL

 

SIGNAL 

INPUT

T/C

A

B

b

Pt100

 

Weight: 

550g / 350g(Aux. Power Code: ADH or ADL) 

 

 

 

 

 Power   

 

 

Please check the voltage of power supplied first, and then connect to 
the specified terminals. It is recommended that power supplied to the 
meter be protected by a fuse or circuit breaker.

 

Power supply: 

AC115/230V,50/60Hz;  

 

 

Optional: 

AC 85~264V, DC 100~300V, DC 20~56V

 

 

Power consumption:

 

5.0VA maximum 

 

Back up memory:

 

By EEPROM 

 

 

 

 

 

 

 
 

„

 

FRONT PANEL 

 

 Power Supply 

 

 
 
 

AC115/230V 

AC85~264V 

Filter or Transformer 

L

N

G

L

N

G

1A Fuse 

9  10 

 

 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

RL 1 
RL 2

RL3 
RL4 

COM 
CI11 

CI2 
CI3 

 

ENT/FN 

 

?  

 

?

 

 

?

 

°C 

Comm. status

Relay status 

Indication

Operation Key

Control Input 

status

Engineer Unit

Display screen

 

 

M.H 

Max. Hold status 

M.H 

Mini. Hold status 

 

  RS485 Communication Port 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

RS485 Port 

31  32 

33 

A B

Max. Distance: 1200M 

Terminate Resistor   

(at latest unit): 

120~300ohm/0.25W 

(typical: 150ohm) 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CSM-321S 

CS2-

V

CSM-321S CSM-

CSM-

CS2-T

CSM-321S CSM-

CSM-

CSM-321S 

CSM-

CSM-321S 

Содержание CS2-T

Страница 1: ...1M ohm Set points Four set points S1 Type S 400 1600 C 1M ohm Control relay Four relays B1 Type B 400 1800 C 1M ohm Relay 2 Relay 3 Dual FORM C 5A 230Vac 10A 115V Relay 1 Relay 4 Dual FORM A 1A 230Va...

Страница 2: ...FN C PANEL CUT OUT 92 0 2 W x 44 0 2 H mm EMC EN 55011 2002 EN 61326 2003 Safety LVD EN 61010 1 2001 CONNECTION DIAGRAM Environmental Operating temp 0 60 C Operating humidity 20 95 RH Non condensing T...

Страница 3: ...as noise or unstable signal User can set the times to average the readings and get smoothly display The meter s sampling is 15cycle sec If the Mavg Moving Average set to be 3 expressed the display up...

Страница 4: ...ading will show the differential value The relay energized with latched function is for electrical safety and human protection For example a current meter relay installed for the over current alarm of...

Страница 5: ...Lo alarm Hi Lo energized hold Go function DO function RL 1 RL2 RL3 RL4 COM ECI1 ECI2 ECI3 ENT FN Kg cm2 R L 1 RL 2 RL3 RL4 COM ECI1 ECI2 ECI3 ENT FN Kg cm2 Analogue output option Remote Display Please...

Страница 6: ...x Mini Hold indication 2 square orange LEDs CO M H displayed When the display function has been selected in Maximum or Minimum Hold function Stickers Each meter has a sticker what are functions and en...

Страница 7: ...4 20 A 2 0 lOsc lOsc Low scale of PV Don t set B 2 0 0 rYsd rYsd Start delay time for Relay energized 0 00 0 9 M 59 9 S C 2 pVhld ecI2 ecI2 External Control Input 2 none reLpv pVhld Mrst rYrst di D 2...

Страница 8: ...hld hIhld do E 1 1 adres adres Device number of the meter 1 255 A 12 0 Pcode Pcode Pass Code for enter Engineer Level 0000 9999 B 12 0 ry hy ry hy Relay 3 Hysteresis 0 5000 counts E 2 9600 baud baud B...

Отзывы: