34
4.8.1 PO function setting
Table 4-8 indicates the setting contents and addresses of PO.
▼
Table 4-8
Parameter assign: select target energy parameter for PO convert output. Two ports of PO
can be set corresponding output parameters.
Pulse divider setting: That is the energy value multiplied by a number to output a pulse.
The setting range is an integer from 1 to 9999, unit is 0.1kWh. For example, set the
divider value to 100, that is each cumulative 100 × 0.1kWh = 10kWh output a pulse.
Pulse width time: That is each pulse high level time. The setting range is 0 ~ 5000, the
unit time is 1mS. When set to 0, the pulse duty cycle is 50%.
Note: The maximum pulse output frequency is 40Hz. If it is test pulse output , it
fi
xed
output 1600 pulses per 1kWh.
4.9 Data logging function
In order to facilitate users to understand the history of the meter, the meter provides
data logging function. Record a set of data at regular intervals. Meter internal 4MB of data
storage space for recording data. The meter has a real-time clock and each data log has a
time stamp.
4.9.1 Data logging function setting
The data logging function can set the parameters to be recorded according to required,
up to 50 parameters can be set. There are 91 parameters to choose, see Table 4-9.