Figure 56: Configure AC/DC Drive Profile AOI
11) The program is now complete.
12) Save, download and run the program.
9.2.13 ControlLogix Example: Read Parameters
This example program will show how to continuously read a block of parameters from the inverter with a
single MSG instruction. Only one read request is outstanding at any given time.
1) Create new Tags.
a)
Double click “Controller Tags” in the controller organizer view.
b)
The “Controller Tags” window appears. Refer to Figure 57.
Figure 57: Create New Tags
c)
Select the “Edit Tags” tab at the bottom.
d)
Create a new tag by entering “connection” in the first blank Name field, and change its Data
Type to “MESSAGE”. This tag will contain configuration information for the MSG instruction.
e)
Select the “Monitor Tags” tab. Expand the “connection” tag by clicking on the “+” sign next to
the tag name. Scroll down to the connection.UnconnectedTimeout field and change its value
from the default 30000000 (30s in 1uS increments) to 1000000 (1s). This value determines
how long to wait before timing out and retransmitting a connection request if a connection
failure occurs.
f)
Collapse the “connection” tag again by clicking on the “-“ sign next to the tag name.
g)
Select the “Edit Tags” tab again. Create another new tag by entering “data_array” in the next
blank Name field, and change its Data Type by typing in “INT[100]” in the Data Type field.
This tag is an array of INTs that will be able to hold up to 100 16-bit parameters from the
inverter. Always make sure that the destination tag size is large enough to hold all elements
to be read.