INSTALLATION

                                                                                                                                                   

DK-2882A / DK-2882B -- Surface Mount Version

DK-2882C / DK-2882D -- Flush Mount Version

PRECAUTIONS

1) Prevent Interference:

The EM Card reader is working at the frequency of 125Khz. Installation precautions are necessary.
i) Make sure the location for installation has no strong low frequency electro-magnetic wave signals. Especially in 
the range of 100-200Khz
ii)  If  there  is  more  than  one  keypads  with  the  same  operation  frequency  installed  closely  in  the  same 
location, make sure that they are at least 30-60cm (1-2ft) apart from each other to prevention interference.

2) Prevent Accidental Short Circuit:

In the previous experience, most of the damages to the keypad are in the installation due to accidental touching of the 
components on circuit board with the wires carrying power. Please be patient and also study the manual to become 
familiar with the specifications of the system before starting the installations.
i) Do not apply power to the system while it is in installation.
ii) Check carefully all the wirings are correct before applying power to the system for testing.

PACKAGE CONTENTS

•  One DK-2882 Keypad
•  Two EM cards
•  One pack of Mounting Screws
•  One Centre Pin Torx Screw Wrench
•  One Wire Harness ( SIx wires)
•  One Programming & Installation Manual

Plastic back box

Plastic inner box

Steel Box

Faceplate

Faceplate

6

An inter-lock system needs two door controllers. This application example uses two DK-2882 with simple cross wire 
connection on their "Output 1 Inhibit" and "Inter-lock Control Output" terminals. It is necessary to
link up the "(-) GND" terminals of the two keypads as common ground to achieve the inter-lock logical functions.

Use keypad to open the door from outside
Press egress button to open the door from inside
Connect the door magnetic sensors on the doors to monitor their positions
While door 1 is open, then, door 2 is forced to keep close, or vice versa
Use N.O. Relay output for fail-secure lock; and N.C. output for fail-safe lock
Please also see the "NOTE" stated in the Application Example (1)

3) BASIC WIRINGS OF AN INTER-LOCK SYSTEM USING TWO KEYPADS

39

Содержание DK-2882

Страница 1: ...demarks and Logos AEI PROTECT ON SYSTEMS LIMITED www apo hk com VANDAL RESISTANT BACK LIT WEATHERPROOF RFID ACCESS CONTROL KEYPAD DK 2882 Programming Installation Manual FOR ELECTRIC LOCK INTER LOCK AND SECURITY SYSTEM INSTALLATIONS ...

Страница 2: ...oor Propped Up Warning The Delay Time Intelligent Egress Button An Unique Feature of A Contemporary Keypad Where And Why Going Out Needs Attention Egress Delay Warning And Alarm Configurations of The Egress Warning And Alarm 4 4 5 6 6 6 7 9 9 9 1 0 1 0 1 0 1 1 1 1 1 2 1 4 1 4 1 5 1 6 1 6 1 6 1 7 1 8 2 0 2 1 2 2 2 3 2 3 2 4 2 4 2 4 2 5 2 5 2 5 2 6 2 6 2 7 2 7 2 APPENDIX DRY CONTACT A dry contact me...

Страница 3: ... The Wiegand Output for Keypad or Reader Mode 9 4 0 Or 9 4 1 Wiegand Output at Keypad Operation Mode Wiegand Code Format for The PIN Code Reading 9 5 0 Or 9 5 1 Wiegand Output Code Format THE 26 BIT WIEGAND DATA OUTPUT READING FROM THE EM CARDS Diagram of The Wiegand Protocol Timing and Its Electrical Manner Example 1 Wiegand Output of Reading An EM Card THE 34 BIT WIEGAND DATA OUTPUT READING FROM...

Страница 4: ...ads compatible with the optional APO Access Controller Indoor or outdoor installation Stand Alone or Inter lock system built in with all the required control logics Controls Going in with PIN and or Card and Going out with programmable egress button Durable steel housing for surface or gooseneck mounting DK 2882A DK 2882B Plastic back box for flush mounting on solid or hollow wooden wall DK 2882C ...

Страница 5: ...O K a b 40 SPECIFICATIONS Operating Voltage 12V 24V AC DC No jumper selection is required for the full voltage range Operating Current 65mA quiescent to 100mA three relays active Environmental Temperature 30 C to 70 C Environmental Humidity 5 95 relative humidity non condensing Working Environment All weather IP 66 Number of Users Output 1 1 000 PIN and or Cards 50 Duress Codes Output 2 100 PIN an...

Страница 6: ...power to the system while it is in installation ii Check carefully all the wirings are correct before applying power to the system for testing PACKAGE CONTENTS One DK 2882 Keypad Two EM cards One pack of Mounting Screws One Centre Pin Torx Screw Wrench One Wire Harness SIx wires One Programming Installation Manual Plastic back box Plastic inner box Steel Box Faceplate Faceplate 6 An inter lock sys...

Страница 7: ...nd terminal 4 is the common point of the two contacts Use N C output for Fail safe locking device and N O output for Fail secure locking device The relay is programmable for Start Stop toggle mode or Momentary timing mode See programming Location 51 for the details 6 7 8 OUTPUT 2 Output Relay 2 1 Amp relay dry contact controlled by the group of PINs or Cards for Output 2 it is an auxiliary output ...

Страница 8: ... A grounding point of the keypad that is common to terminal 2 16 DOOR SENS N C Door Position Sensing Input Normally Close A Normally Closed N C sensing point referring to ground with the help of a normally closed magnetic contact monitors the open or close status of the door It initiates the following functions for the system a Door Auto Re lock The system immediately re locks the door after it is...

Страница 9: ...m status STATUS TONES LED SIGNALS 1 On Programming Mode ON 2 Successful Key Entry 1 Beep 1 Flash 3 Successful Code Card Entry 2 Beeps 2 Flashes 4 Unsuccessful Code Card Entry 5 Beeps 5 Flashes 5 Power Up Delay Continuous Beeps Continuous Flashes 6 Output Relay Activation 1 Second Long Beep 7 On Standby 1 Flash in 2 Seconds Interval 8 System Refreshing Fast Flashes for 1 Minute 9 Card or PIN Alread...

Страница 10: ...the details of programming a new master code NOTE If the keypad is linking up with the DA 2800 controller in the Split decoded operation it is necessary to put the controller s Link up Jumper to ON position to get the new Master Code for it As the Master Code is also the link up code of the two units Do Not Forget to put the Link up jumper back to OFF position after the programming Otherwise the c...

Страница 11: ... contact your local agent if purchase of the DA 2800 Controller is required DK 2882 IN SPLIT DECODED OPERATION 34 RF WIRELESS REMOTE CONTROL DOOR LOCK GARAGE DOOR OPENER SECURITY SYSTEM AUTOMATIC OPERATOR COMMON GROUND COMMON GROUND DA 2800 CONTROLLER DK 2882 DK 2882 MAXIMUM 4 DK 2882 CAN BE CONNECTED IN PARALLEL DATA I O DATA I O EXIT DA 2800 ACCESS CONTROLLER REFRESH THE SYSTEM WITH THE REFRESHI...

Страница 12: ... the 1 000 User IDs for the User PIN Card from 000 999 d Read Card Put the Card close to the card reader e Confirm the card is read 2 beeps the Common User Code goes to this User ID automatically f A Common User Code for example 8 6 2 5 MUST be set at the Programming Location 03 first for this operation mode The code can be used for all the EM Cards in this operation mode 0000 01 3289 10 2 002 832...

Страница 13: ... Consultants can select the 34 bits Wiegand data output in Binary format code 950 or BCD format 951 in the PIN Code entry for product design The 34 bit and the 26 bit Wiegand signals are transmitted in the same electrical manner and timing standard The 34 bit Wiegand protocol for PINs has 1 first parity bit 32 bits for the PIN code and 1 stop bit for a total of 34 bits The first parity bit is an E...

Страница 14: ...ith a Department User Code A lost Card can be used only by the people in the same group who know the Department Code iii EM Card Secondary User PIN Each EM Card has its own proprietary User PIN A lost Card can not be used by other people NOTE Each EM Card is a Prime card and it has the priority to be read The system provides the proprietary Wiegand Data output from each card faithfully The Seconda...

Страница 15: ...a Output in BCD Code The system provides a 34 bits Wiegand data output in BCD code format for each PIN Code reading WIEGAND O P MODE LOCATION OUTPUT CODE FORMAT VALIDATION VALIDATION LOCATION 95 0 or 1 94 0 or 1 30 Example User Name Location Function Code User ID PIN Code Card Remark 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 000 RECORD A MASTER CODE Location 01 MASTER CODE Master Code is the author...

Страница 16: ...tion number and 4 to 8 Digits SUPER USER PIN SUPER USER PIN SUPER USER PIN SUPER USER PIN COMMON USER PIN VALIDATION LOCATIONS 11 12 13 21 03 1357 03 03 04 05 03 05 16 THE WIRE HARNESS FOR WIEGAND DATA OUTPUT APO DATA I O NOTE The information in this section is NOT for the system in Stand Alone operation It is not necessary to plug in the wire harness to the socket just leave it open The informati...

Страница 17: ...re allowed in group 2 for O P 2 Group 3 For User PINs Cards Controlling Output 3 100 Users are allowed in group 3 for O P 3 SELECTION OF OPERATION MEDIA Number 1 2 3 or 4 represents the Media to be used to operate the keypad Number 5 is the authorization code for deleting of an PIN and or Card from its User ID EM Card only Private User PIN only EM Card Secondary User PIN EM Card Common User PIN De...

Страница 18: ...silent area The people have to wait for the door open until the delay time reaches 2 Momentary Contact Mode with Warning Beep Press the Button once The system gives Warning Beeps during the Egress Delay Good for the place required attention The keypad beeps during the people are waiting for the door open 3 Momentary Contact Mode with Warning Beep Alarm Press the Button once The system gives Warnin...

Страница 19: ...en to a high traffic passage An egress button with short delay and warning beeps helps the user to pay attention to the people passing by to prevent hitting them when the door is pushed outward Emergency Exit Emergency Exit is not open to the public for daily use It is for emergency case only It is usually closed and watched by the security guards The egress button of this keypad can be programmed...

Страница 20: ...sitor Code e Entry Confirmation Read Card Duress Code 4 8 DIGITS 40 01 50 00 or 01 99 VISITOR CODE VALIDATION LOCATION VISITOR ID VALID PERIOD 20 STATUS LED FLASHING ON OFF IN STANDBY Location 73 STANDBY FLASHING ON OFF Some people find the flashing light of the status LED the amber LED is annoying during the keypad is on standby especially at the night time The standby flashing can be ON OFF with...

Страница 21: ...he 1 second long notification beep is replaced by 2 short beeps when the output is activated with a valid Card Code No beep is given if output is activated with Egress Button The 2 short beeps are cancelled while the Pacifier Tone OFF mode in the Location 71 is selected FUNCTION MODES VALIDATION LOCATION FUNCTION MODES VALIDATION LOCATION 1 or 0 1 or 0 71 72 24 Example 3 Delete a Visitor Code from...

Страница 22: ...ss Code the Amber LED keeps flashing b Key in the Duress Codes 3 3 6 9 for operating the Output 1 c Confirm it with the key Output 1 activates in a normal way and the Duress Output also activates to report Duress Event to an alarm system if connected NOTE No Duress Event can not be reported in the operation of only EM Card alone Read Card 22 CONFIGURATION OF THE OUTPUT MODES OF OUTPUT 1 2 AND 3 Lo...

Отзывы: