Duo-i6515/6525/8030NM
User Manual V1.6
Advanced RF Technologies, Inc. Proprietary Document
Page 24 of 40
- Uplink AGC Level
Duo-i6515NM: 5 to 15 dBm @ 0.5 dB step, default value: 15 dBm
Duo-i6525NM: 15 to 25 dBm @ 0.5 dB step, default value: 25 dBm
Duo-i8030NM: 20 to 30 dBm @ 0.5 dB step, default value: 30 dBm
- Uplink Tracking Offset (0 to 10 dB @ 0.5 dB step, default value is 3 dB)
System
-
If you click the
Reboot
button, the following message box will appear:
When the system reboots, the latest settings will be saved.
Please wait approximately 30 seconds to 1 minute for the system to reboot.
-
If you click the
Factory Setting
button, the following message box will appear:
Factory setting will erase the settings saved by the user and change all the
parameters to the factory default settings.
Heartbeat Time
- Heartbeat on and off (Default mode is Off)
- Heartbeat periodic time (Range: 1 to 59 min @ 1 min step,
default time is 20 min)
Alarm Setting
-
RSSI Alarm at Donor (-95 ~ -50 dBm @ 0.5 dB step)
-
Default value ;
- Duo-i6515/6525NM : -75 dBm
- Duo-i8030NM : -90 dBm
- RF Power Alarm (2 ~ 10 dB @ 0.5 dB step, default value: 6 dB)