Page 8
TABLE 1
UNIT CLEARANCES TO COMBUSTIBLE MATERIALS
Unit
Top
Side**
Bottom
Back
Flue
in
mm
in
mm
in
mm
in
mm
in
mm
030/105
1
25
1
25
1
25
18
457
6*
152
125/400
6
152
18
457
1
25
18
457
6
152
*6” is for single wall. Double wall B-vent clearance will be
in accordance with the manufacturer’s listing.
**Access panel or control box side of unit should have
24”
(610mm) clearance.
The Commonwealth of Massachusetts stipulates the fol-
lowing additional requirements:
1 - Gas furnaces shall be installed by a licensed
plumber or gas fitter only.
2 - T
he gas cock must be “T handle” type.
The appliance shall not be installed downstream from
evaporator coils or cooling units.
Install the unit in the desired location as governed by
clearances, vent connection, air direction, gas supply,
electrical supply and service accessibility.
Unit is shipped ready for installation.
UHCM -125/400 UNITS
Four mounting nuts are furnished. Refer to dimension
illustration. Mounting nuts will accommodate 3/8” x 16
threaded rods.
1 - Push each louver to the left to depress spring and
release locking tab on the other end (locking tab
keeps the louver in place for shipping).
2 - Rotate louvers to direct airflow as desired.
3-
Cut threaded rods to desired length and slide a 3/8”
nut onto the rod.
4 - Slide a flat washer onto the threaded rod AFTER the
nut (7/16” inside diameter X 1” outside diameter X
1/16” thick washer).
5 - Screw the rods (two or four) into the mounting nuts
on the unit.
6 - Tighten nuts to secure unit to rods.
TABLE 2
MAXIMUM MOUNTING HEIGHTS - 125/400
UHRS 30/105
Unit may be installed as shown in figure 1 or rotated
180°.
1 - Push each louver to the right to depress spring and
release locking tab on the other end (locking tab
keeps the louver in place for shipping).
2 - If installing unit in a rotated position - release locking
tabs in the same manner as previous step. Rotate
each louver 180° and reinstall. Remove and retain
screws securing access panel. Rotate access panel
180° and resecure using retained screws.
3 - Rotate louvers to direct airflow as desired.
4 - Choose location for mounting brackets.
5 - Align mounting brackets with pilot holes on the top or
bottom (when rotating) edge of the unit. Secure with
screws provided in bag assembly.
6 - To support unit, secure mounting bracket to ceiling
joist or truss. Unit may also be supported using
support rods as shown in figure 1.
INSTALL UNIT HEATER
(030 / 105 SHOWN)
MOUNTING
BRACKETS
(2)
SUPPORT
RODS
ACCESS PANEL
FIGURE 1
Adequate facilities for supplying air for combustion and
ventilation must be provided in accordance with the cur-
rent edition of ANSI Z223.1, section 5.3 and CSA-B149
installation compliance codes, or applicable provisions of
local building codes.
All gas-fired appliances require air to be used for com-
bustion. In many buildings today, there is a negative in-
door air pressure caused by exhaust fans, etc. If sufficient
quantities of combustion air are not available, the heater
Additional Requirements
Unit Heater Installation
Combustion and Ventilation Air
Unit
Feet (Meters)
UHCM-125/150
16 (4.9)
UHCM-175/200
20 (6.1)
UHCM- 250/400
30 (9.1)
Содержание UH Series
Страница 3: ...Page 3 UHRS COMPACT UNIT HEATER PARTS ARRANGEM ENT 030 105K BTUH TRANSFORMER ...
Страница 6: ...Page 6 UHCM STANDARD UNIT HEATER PARTS ARRANGEMENT 125 400K BTUH ...
Страница 12: ...Page 12 ...
Страница 24: ......