Adp UH Series Скачать руководство пользователя страница 14

Page 14

 

 

8 - If B-1 vent or an insulated flexible vent pipe cannot 

be used as liners,  the  chimney  must  be  rebuilt  
to  accommodate  one  of  these  methods  or  some 
alternate approved method must be found to vent the 
appliance. When inspection reveals that an existing 
chimney  is  not  safe  for  the  intended  purpose,    it 
shall be rebuilt to conform to nationally recognized 
standards,  lined  or  relined  with  suitable  materials   
or replaced with a gas vent or chimney suitable for 
venting unit heaters. The chimney passageway must 
be checked periodically to ensure that it is clear and 
free of obstructions.

 

REMOVAL OF UNIT FROM COMMON VENT

 

In the event that an existing unit heater is removed from a 
venting system commonly run with separate gas applianc- 
es, the venting system is likely to be too large to properly 
vent the remaining attached appliances. The following test 
should be conducted while each appliance is in operation 
and the other appliances are not in operation, yet remain 
connected to the common venting system. If the venting 
system has been installed improperly, the system must be 
corrected.

 

1 -  Seal any unused openings in the common venting 

system.

 

2 - Visually inspect the venting system for proper size and 

horizontal pitch. Determine there is no blockage or 
restriction, leakage, corrosion, or other deficiencies 
which could cause an unsafe condition.

 

3 - In so far as is practical, close all building doors and 

windows and all doors between the space in which 
the appliances remaining connected to the common 
venting system are located and other spaces of the 
building. Turn on clothes dryers and any appliances 
not connected to the common venting system. Turn 
on  any  exhaust  fans,  such  as  range  hoods  and 
bathroom exhausts, so they will operate at maximum 
speed. Do not operate a summer exhaust fan. Close 
fireplace dampers.

 

4 - Follow the lighting instructions. Place the appliance 

being inspected in operation. Adjust thermostat so 
appliance will operate continuously.

 

5 - Test for spillage at the draft hood relief opening after 

five minutes of main burner operation. Use the flame 
of  a  match  or  candle,  or  smoke  from  a  cigarette, 
cigar, or pipe.

 

6 -  After  it  has  been  determined  that  each  appliance 

remaining connected to the common venting system 
properly vents when tested as outlined above, return 
doors,  windows,  exhaust  fans,  fireplace  dampers 
and any other gas-burning appliance to their previous 
condition of use.

 

7 - If improper venting is observed during any of the above 

tests, the common venting system must be corrected. 
The common venting system should be resized to ap- 
proach the minimum size as determined by using the 
appropriate tables in Appendix G in the current editions 
of the ANSI Z223-1, or the appropriate Category I Nat- 
ural Gas and Propane appliances venting sizing tables 
in the current standards of the CSA-B149 for installa- 
tion compliance codes.

 

 

 

NOTE - Local codes may supersede any of the provisions 
outlined in this instruction.

 

The  UH(RS,CM)  series  unit  heaters  use a direct spark 
ignition system. There is no pilot necessary as the spark 
lights the main burner as the gas valve is turned on. The 
direct spark ignition control board emits radio noise as the 
sparking process is under way. The level of energy may 
be sufficient to disturb a logic circuit in a microprocessor 
controlled  thermostat. It is recommended that an isola- 
tion relay be used when connecting the unit heaters to a 
microprocessor controlled thermostat. Install the thermo- 
stat according to instructions provided. Install a separate 
fused disconnect switch, with the fuse sized according to 
blower motor size. Connect wiring through knockout on 
the junction box located on the side of the unit heater. Re- 
fer to dimensions in the front of this instruction for location. 
Refer to heater wiring diagram for connection information. 
Use 18 gauge wire or larger for thermostat connections.

 

NOTE - 

Electrically ground unit in accordance with local 

codes or, in the absence of local codes, in accordance 
with the current editions of the ANSI/NFPA No. 70, Na- 
tional Electrical Code or CSA C22.1, Canadian Electrical 
Code, Part 1.

 

NOTE  - 

Uninsulated  ground  wires  must  be  wrapped  in 

electrical tape to avoid damage to the electrical system. 

Make line voltage connections as shown in figure 7. Con- 
nect field wiring as shown on wiring diagram on unit. Also 
refer to typical diagram in this manual. An additional ther- 

mostat wire must be run to terminal “G” on heater when 
continuous blower is desired.

 

 

 

Electrical Connections

 

Содержание UH Series

Страница 1: ... HEATERS 507938 01 6 2019 Gas Connection 18 Leak Check 18 Unit Start Up 18 To Turn Off Gas to Unit 19 Heating Sequence of Operations 19 Ignition Control LED 20 HighAltitudeAdjustments 20 Gas Flow 20 Gas Pressure Adjustments 20 Limit Control Switch 21 Louver VaneAdjustment 21 Combustion AirPressure Switch 21 Flame Rollout Switch 21 Service 21 Start Up and Performance Checklist 22 RETAIN THESE INSTR...

Страница 2: ...E ACCESS PANEL ADJUSTABLE LOUVERS Model No A B C in mm in mm in mm UHRS 030A UHRS 045A 12 3 8 314 6 1 2 165 3 7 8 98 UHRS 060A UHRS 075A 17 1 2 445 6 1 4 159 6 1 8 156 UHRS 090A UHRS 105A 23 584 7 7 8 200 9 1 8 232 1 2 13 UHRS 030 105 DIMENSIONS Inches mm MOUNTING SLOTS Typical 5 16 x 3 Inches 8 x 76 mm 10 1 2 267 SIDE VIEW 1 25 4 1 4 108 HANGING BRACKETS 2 8 3 4 222 2 3 4 70 ...

Страница 3: ...Page 3 UHRS COMPACT UNIT HEATER PARTS ARRANGEM ENT 030 105K BTUH TRANSFORMER ...

Страница 4: ...0 25 635 23 3 4 603 9 1 2 241 3 76 UHCM 125 200 DIMENSIONS Inches mm 16 406 10 1 2 5 3 8 D 1 2 13 3 1 8 79 4 3 8 16 MOUNTING NUTS FOR UNIT SUSPENSION TOP VIEW 2 1 2 64 ELECTRICAL INLETS ADJUSTABLE LOUVERS COMBUSTION AIR INDUCER FLUE OUTLET A 31 7 8 810 10 5 8 270 DIRECT DRIVE FAN 35 1 4 895 AIR FLOW HEAT EXCHANGER GAS VALVE FRONT VIEW SIDE VIEW ...

Страница 5: ... 521 1 2 13 C B FLUE OUTLET 4 3 8 16 MOUNTINGNUTS FOR UNIT SUSPENSION 1 2 13 3 1 8 79 DIRECT DRIVE FAN 35 1 4 895 AIR FLOW HEAT EXCHANGER GAS VALVE FRONT VIEW SIDE VIEW 10 5 8 270 COMBUSTION AIR INDUCER ADJUSTABLE LOUVERS TOP VIEW 31 7 8 810 2 5 8 67 ELECTRICAL INLETS 3 76 5 3 8 137 267 10 1 2 UHCM 250 400 DIMENSIONS Inches mm 16 406 A ...

Страница 6: ...Page 6 UHCM STANDARD UNIT HEATER PARTS ARRANGEMENT 125 400K BTUH ...

Страница 7: ...MA 02269 9101 These instructions are intended only as a general guide and do not supersede local codes in any way Authorities having jurisdiction shouldbeconsulted beforeinstallation The installation must conform with local building codes or in the absence of local codes with the current edition of CSA B149installation compliancecodes Allelectrical wir ing and grounding for the unit must also comp...

Страница 8: ...the unit 6 Tighten nuts to secure unit to rods TABLE 2 MAXIMUM MOUNTING HEIGHTS 125 400 UHRS 30 105 Unit may be installed as shown in figure 1 or rotated 180 1 Push each louver to the right to depress spring and release locking tab on the other end locking tab keeps the louver in place for shipping 2 If installing unit in a rotated position release locking tabs in the same manner as previous step ...

Страница 9: ...ovisions GENERAL RECOMMENDATIONS AND REQUIREMENTS Unit heaters must be vented in compliance with the lat est edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 in the USA and with CSA B149 1 codes in Canada as well as applicable provisions of local building codes and the following instructions 030 150 Units The transition isa part of the combus tion air blower 175 400 Units A stamped extrud...

Страница 10: ...K 200K 250K 300K Btuh units 6 152mm on 360 400K Btuh units On 175 400 units a flue transition piece supplied is required to fit over the outlet of the induced draft assembly on the appliance NOTE If needed loosen the upper right two or three screws securing thecombustion air blower Slide thetran sition into place and secure loosened screws 3 Keep the vent connector runs as short as possible with a...

Страница 11: ...nd block to protect the vent termination from direct winds 6 Horizontal vent termination must be free from obstructions and at least 12 305mm above grade level and maximum snow height 7 Do not install a horizontal vent termination directly below roof eaves or above a public walkway or any other area where condensate dripping may be troublesome and may cause some staining Avoid windows where steam ...

Страница 12: ...Page 12 ...

Страница 13: ...rmanently sealed 2 A fan assisted unit heater may be commonly vented into an existing lined masonry chimney provided a The chimney is currently serving at least one draft hood equipped appliance b The vent connector and chimney are sized in accordance with venting tables 3 A B1 double wall vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof assem...

Страница 14: ...fter it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers andany othergas burningappliancetotheirprevious condition of use 7 If improperventing is observed during any of the above tests the common venting system must be corrected The common venting system should b...

Страница 15: ...E THERMOSTAT CONNECTIONS 24V POWER R R R 24V COMMON C C C P365 AND P364 ARE ENERGIZED SIMULT A N E O U SL Y P374 4 1 1 3 BLOWER G G G HEAT W1 W1 W1 W2 W2 FIELD PROVIDED CLASS II 24VAC THERMOSTAT WIRING Model UHRS Unit Heater Separated Combustion Unit Heater Heat Input 030k 105k BTUH Voltage 120 60 1 Supersedes N A Form No 537992 01 Rev 0 06 07 08 05 04 YEL 03 WHT 02 01 0 C O P366 J 366 P367 J 367 ...

Страница 16: ...MOSTAT CONNECTIONS 24V POWER R 24V COMMON C BLOWER G HEAT W1 R R C C G G W1 W1 W2 W2 P365 AND P364 ARE ENERGIZED SIMULT A N E O U SL Y P374 1 4 FIELD PROVIDED CLASS II 24VAC THERMOSTAT WIRING Model UHRS Unit Heater Separated Combustion Unit Heater Heat Input 125k 200k BTUH Supersedes N A Form No 538025 01 Rev 0 02 120 60 1 Voltage 08 07 06 05 04 03 01 YEL WHT 0 P366 J 366 P367 J 367 P363 J 363 W H...

Страница 17: ... C OM 6 6 XFMR 24VAC R R C C P364 2 5 8 P365 2 5 8 2 J374 1 4 P374 1 4 BLOWER G G G HEAT W1 HEAT W2 1 FIELD PROVIDED CLASS II 24VAC THERMOSTAT WIRING W1 W1 W2 W2 Model UHCM Unit Heater Separated Combustion Unit Heater Heat Input 250k 400k BTUH Voltage 120 60 1 Supersedes N A Form No 538024 01 Rev 0 01 WHT 06 07 08 05 04 03 02 YEL WHT 0 P366 J 366 P367 J367 P363 J 363 W H T GR N Y E L BLK W H T S 4...

Страница 18: ... power to unit These devices should be properly labeled by the installer Unit Start Up FOR YOUR SAFETY READ BEFORE LIGHTING WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water WARNI...

Страница 19: ... the combustion air inducer starts immediately 2 Combustion air pressure switch proves inducer operation before allowing ignition sequence to start This switch is factory set and no adjustment is necessary 3 After pre purge of approximately 30 seconds the spark ignition is energized and the solenoid valves open in the gas valve 4 The spark then ignites the gas the ignition sensor proves the flame ...

Страница 20: ...t pressure regulator to pressure shown in table 6 In the US units may be fired at full input up to 2000 feet 610m above sea level Above 2000 feet 610m unit must be de rated by four percent per 1000 feet for instal lation above 2000 feet The de rate may be accomplished by adjusting the manifold pressure See table 7 See the Engineering Handbook for high altitude kit part numbers TABLE 7 TABLE 6 In s...

Страница 21: ... on electrode and adjust if required The gap should be between 0 110 and 0 140 3mm to 4mm The gap may be checkedwithappropriatelysizedtwistdrills or feeler gauges d Reinstall burner cluster assembly burner box top gas manifold hightensionandsensorleads Reconnect gas supply piping e Restore electrical power and gas supply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY...

Страница 22: ... times beforelocking out the gas valve which will be indicated by two flashes on the LED 6 Torestart the system de energize the thermostat call for heat and follow the operating instructions under Unit Start Up and Operation REPAIR PARTS When ordering repair parts include the complete unit model number listed on the unit rating plate For ex ample UHRS 45A 1 Contact the installing dealer or visit w...

Страница 23: ...ranty period for the specific component ADP at its option will furnish a replacement heat exchanger or allow a credit in the amount of the heat exchanger original selling price toward the purchase of a new ADP unit heater No extended coverage granted for UHCM series heat exchangers For information on this products warranty including complete warranty terms registering for an extended warranty or i...

Страница 24: ......

Отзывы: