![Admag AX01C Скачать руководство пользователя страница 40](http://html1.mh-extra.com/html/admag/ax01c/ax01c_installation-manual_2852895040.webp)
<4. Wiring>
39
IM 01E25A01-01EN
(2) Input signals
Input signal type
Specification
Status input [Sin]:
IMPORTANT
The status input detects a signal without voltage.
Loading voltage during the switching status "Close" may result in damage on the electrical
circuit.
The status input is used for connecting to the following no-voltage contacts.
Switching status
Resistance
Closed
200 Ω or less
Open
100 kΩ or more
Transmitter
Sin-
Sin+
F0447.ai
Figure 4.6.9 Connection diagram: Status input [Sin]
W
iring
4