Industrial
Electronic Devices
ADFweb.com Srl – IT31010 – Mareno – Treviso INFO:
www.adfweb.com
Phone +39.0438.30.91.31
User Manual
PROFIBUS Master / Modbus TCP Slave - Converter
Document code: MN67579_ENG Revision 2.002 Page 24 of 32
O
PTIONS
:
The section “Options” is used to enable some option for each PROFIBUS device (Fig. 13).
The means of the fields are:
In the field “
Enable Sync
” the
PROFIBUS Sync command is
enable. This option is enable only
if the “Sync Mode” is supported
by the device (see Capabilities
section to check it);
In the field “
Enable Freeze
” the
PROFIBUS Freeze command is
enable. This option is enable only
if the “Freeze Mode” is supported
by the device (see Capabilities
section to check it);
In the field “
Reset data if
PROFIBUS
master
loses
communication
with
the
slave
” is possible to select to
cancel the data of the slave if the
Master lost the connection with
the device;
In the field “
Reset data if
Modbus Master doesn’t poll
data
the
slave
in
...
milliseconds
” is possible to
select to cancel the data sended
to the slave PROFIBUS if the
Converter
don’t
receive
a
Ethernet frame within the time
expressed in the field.
Figure 13: “PROFIBUS Device – Options” window