The data of the columns in the “Transmit PDO” have the following meanings:
In the Field "
Cob-ID
" the address for
the PDO is defined;
In the Field "
Dimension
" the dimension
of the PDO is defined (it can be
between 1 and 8);
In the Field "
Add B1
" the first byte
where the data will be loaded in the
LoRaWAN array is defined;
In the Field "
Add B2
" the second byte
where the data will be loaded in the
LoRaWAN array is defined (only if
Dimension
> 1);
In the Field "
Add B3
" the third byte
where the data will be loaded in the
LoRaWAN array is defined (only if
Dimension
> 2);
In the Field "
Add B4
" the fourth byte where the data will be loaded in the LoRaWAN array is defined (only if
Dimension
> 3);
In the Field "
Add B5
" the fifth byte where the data will be loaded in the LoRaWAN array is defined (only if
Dimension
> 4);
In the Field "
Add B6
" the sixth byte where the data will be loaded in the LoRaWAN array is defined (only if
Dimension
> 5);
In the Field "
Add B7
" the seventh byte where the data will be loaded in the LoRaWAN array is defined (only if
Dimension
> 6);
In the Field "
Add B8
" the eighth byte where the data will be loaded in the LoRaWAN array is defined (only if
Dimension
> 7);
In the Field “
Send Time
” insert the interval used to send the PDO. The time is in milliseconds;
If the field “
On Change
” is checked, the gateway send the Transmit PDO when the data change the value;
In the field "
Mnemonic
" the description for the PDO is defined.