Industrial
Electronic Devices
ADFweb.com S.r.l.
User Manual
BACnet Master / SNMP Agent
Document code: MN67726_ENG Revision 1.100 Page 36 of 42
Writing BACnet data from SNMP
:
In order to write the data to the HD67726 it is necessary to use the “snmpset” command. The Output array is contained to this internal
directory: 1.3.6.1.4.1.33118.1.1.1.4.x.0, where ‘x’ is the number of data block. Each data block has a dimension of 128 bytes.
Example: you want to write informations of the data block 3 with the data ‘0123456789’ (ASCII). The structure of the command to send is:
snmpset –v1 –cprivate “IP Address of the converter” 1.3.6.1.4.1.33118.1.1.1.5.3.0 s “0123456789”