SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, BACnet and SNMP.
By Pressing the “
Set Communication
” button from the main window for SW67726 (Fig. 2) the
window “Set Communication” appears (Fig. 3).
In the section “BACnet Type” is possible to select the type of BACnet to use from:
BACnet/IP (over Ethernet);
BACnet MS/TP (over RS485).
If selected “BACnet/IP” the means of the fields for “BACnet” are:
In the field “
IP ADDRESS
” the IP address of the converter is defined;
In the field “
SUBNET
Mask
” the SubNet Mask of the converter is defined;
In the field “
GATEWAY
” the default gateway of the network is defined. This feature can be
enabled or disabled pressing the Check Box field. This feature is used for going out of the net;
In the field “
Port
” the port number used for BACnet communication is defined. The default port
used for BACnet communication is 47808, but is possible to insert any value (except 10000 and
10001);
In the field "
BACnet Device Name
" the name of the BACnet side of the converter is defined;
In the field “
Device Identifier
” the ID of the BACnet/IP side of the converter is defined (used
for the Device Identifier).
Figure 3a: “Set Communication” window