Figure 4: “Set EtherNet/IP Slaves Access” window
ETHERNET/IP ACCESS:
By Pressing the “
EtherNet/IP Access
” button from the main window for SW67665 (Fig. 2) the window “Set EtherNet/IP Slaves Access”
appears (Fig. 4).
This section is used to define the list of the EtherNet/IP slaves to read/write with the BACnet Master.
The means of the fields are:
If the field “
Enable
” is checked, the polling to the EtherNet/IP slave is enabled;
In the field “
IP Address
” the IP Address of the EtherNet/IP slave is defined;
In the field “
Start Input
” the starting Input byte of the EtherNet/IP slave to map on BACnet side is defined;
In the field “
Num Input
” the number of consecutive Input byte to map on BACnet side is defined;
In the field “
Start Output
” the starting Output byte of the EtherNet/IP slave to write from BACnet side is defined;
In the field “
Num Output
” the number of consecutive Output byte to write from BACnet side is defined;
In the field “
Time Poll
” the polling time in ms is defined;
In the field “
Instance T > O
” the instance of the assembly for the Target to Originator data direction is defined;
In the field “
Conn. Point T > O
” the connection point of the assembly for the Target to Originator data direction is defined;
In the field “
Instance O > T
” the instance of the assembly for the Originator to Target data direction is defined;
In the field “
Conn. Point O > T
” the connection point of the assembly for the Originator to Target data direction is defined;
In the field “
Mnemonic
” a brief description is defined.