SET COMMUNICATION:
This section define the fundamental communication parameters of two buses, BACnet
and EtherNet/IP.
By Pressing the “
Set Communication
” button from the main window for SW67689
(Fig. 2) the window “Set Communication” appears (Fig. 3).
In the field “Type” is possible to select the type of BACnet to use from:
BACnet/IP (uses Ethernet);
BACnet MS/TP (uses RS485).
If selected “BACnet/IP” the means of the fields for “BACnet Slave” are:
In the fields “
IP ADDRESS
” the IP address of BACnet/IP side of the converter
is defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of BACnet/IP side of the
converter is defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This
feature can be enabled or disabled pressing the Check Box field. This feature is
used for going out of the net;
In the field “
Port
” the port used for BACnet communication is defined. The
default port used for BACnet communication is 47808, but is possible to insert
any value (except 10000 and 10001);
In the field "
BACnet Device Name
" the name of BACnet/IP side of the
converter is defined;
In the field “
Device Identifier
” the ID of BACnet/IP side of the converter is
defined;
If the field “
BACnet description up to 32 chars
” is checked, the description
for the BACnet Objects can be up to 32 chars long.
Figure 3a: “Set Communication” window