UPDATE VIA SERIAL (only for hardware with jumpers):
By pressing the “
Update Via Serial
” button it is possible to load the created configuration into the device, and also the Firmware if is
necessary. This by using the RS232 port.
In order to load the parameters or update the firmware in the device, follow these instructions:
Turn OFF the Device;
Connect the RS232 Null Modem cable form your PC to the Converter;
Put Dip2 of ‘Dip-Switch A’ in ON position;
Select the “
COM port
” and press the “
Connect
” button;
Turn ON the device;
Check the “Device state” Led. It must blink quickly (see “LEDS” section);
Press the “
Next
” button;
Select which operations you want to do.
Press the “
Execute Update Firmware
” button to start the upload;
When all the operations are “OK”, turn OFF the device;
Put Dip2 of ‘Dip-Switch A’ in OFF position;
Disconnect the RS232 cable;
Turn ON the device.
At this point the configuration/firmware on the device is correctly updated.