Industrial

 

Electronic Devices 

 

 

 ADFweb.com S.r.l.           

 

 

User Manual   

M-Bus master / Modbus slave - Converter

 

 

Document code: MN67029_ENG     Revision 3.000   Page 28 of 47

 

 

 

Example: 
 

 0x68 - Start Byte 
 0xBD - L Fied 
 0xBD - L Field 
 0x68 - Start Byte 
 0x08 - C Field 
 0x02 - A Field 
 0x72 - CI Field 
  
 0x71 - Identification Number (Byte 4of4) 
 0x65 - Identification Number (Byte 3of4) 
 0x45 - Identification Number (Byte 2of4) 
 0x28 - Identification Number (Byte 1of4) 
 0x4D - Manufacturer (Byte 2of2) 
 0x6A - Manufacturer (Byte 1of2) 
 0x81 - Version 
 0x04 - Medium 

 

 0x3E - Access Number 
 0x27 - Status 
 0x00 - Signature (Byte 2of2) 
 0x00 - Signature (Byte 1of2) 
 
 0x04 - DIF 
 0x79 - VIF  

 Identification 

 0x00 - Data (Byte 4of4)  
 0x00 - Data (Byte 3of4)  
 0x00 - Data (Byte 2of4)  
 0x00 - Data (Byte 1of4) 
 
 0x04 - DIF 
 0x06 - VIF  

 Energy 

 0x00 - Data (Byte 4of4) 
 0x00 - Data (Byte 3of4) 
 0x00 - Data (Byte 2of4) 
 0x00 - Data (Byte 1of4) 
  
 0x44 - DIF 
 0x06 - VIF  

Energy 

 0x00 - Data (Byte 4Of4)  
 0x00 - Data (Byte 3Of4)  
 0x00 - Data (Byte 2Of4)  
 0x00 - Data (Byte 1Of4) 
 … 
 …   Other Variables 
 … 
 0x55 - Check Sum 
 0x16 - Stop Byte 

Fixed Data Header 

First Variable ( 1 ) 

Second Variable ( 2 ) 

Third Variable ( 3 ) 

To be use in the “

Position

” field 

Identification Number (or Secondary Address) put in the 
selected register if “

Identification Number

” is checked 

Status of the meter put in the selected register if “

Node

 

State

” is checked 

Содержание HD67029-B2-232-160

Страница 1: ...029 B2 485 80 www adfweb com Price HD67029 B2 485 160 www adfweb com Price HD67029 B2 485 250 Benefits and Main Features Very easy to configure Electrical isolation Temperature range 40 C 85 C 40 F 18...

Страница 2: ...TED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recent...

Страница 3: ...The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and ope...

Страница 4: ...Industrial Electronic Devices ADFweb com S r l User Manual M Bus master Modbus slave Converter Document code MN67029_ENG Revision 3 000 Page 4 of 47 EXAMPLE OF CONNECTION...

Страница 5: ...ial Electronic Devices ADFweb com S r l User Manual M Bus master Modbus slave Converter Document code MN67029_ENG Revision 3 000 Page 5 of 47 CONNECTION SCHEME Figure 1a Connection scheme for HD67029M...

Страница 6: ...Industrial Electronic Devices ADFweb com S r l User Manual M Bus master Modbus slave Converter Document code MN67029_ENG Revision 3 000 Page 6 of 47 Figure 1b Connection scheme for HD67029M 485 20...

Страница 7: ...Industrial Electronic Devices ADFweb com S r l User Manual M Bus master Modbus slave Converter Document code MN67029_ENG Revision 3 000 Page 7 of 47 Figure 1c Connection scheme for HD67029 B2 232 xxx...

Страница 8: ...Industrial Electronic Devices ADFweb com S r l User Manual M Bus master Modbus slave Converter Document code MN67029_ENG Revision 3 000 Page 8 of 47 Figure 1c Connection scheme for HD67029 B2 485 xxx...

Страница 9: ...to 80 M Bus devices HD67029 B2 232 160 or HD67029 B2 485 160 support up to 160 M Bus devices HD67029 B2 232 250 or HD67029 B2 485 250 support up to 250 M Bus devices In the case of HD67029 B2 xxx 160...

Страница 10: ...on depends to the code of the device For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 15V 21V 18V 35V Consumption at 24V DC Device No Load W VA Full Load W VA HD67029M xxx 20 3 5...

Страница 11: ...st with Dip2 of Dip Switch A at OFF position for HD67029M xxx 20 or with Dip1 of Dip Switch A at OFF position for HD67029 B2 xxx xxx is used for the normal working of the device The second with Dip2 o...

Страница 12: ...0 device has got four LEDs that are used to give information of the functioning status The various meanings of the LEDs are described in the table below LED Normal Mode Boot Mode 1 Device state green...

Страница 13: ...een Blinks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Not used OFF Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 M Bus Comm Blinks whe...

Страница 14: ...t example one from a personal computer must be made with a Null Modem cable a serial cable where the pins 2 and 3 are crossed It is recommended that the RS232 cable not exceed 15 meters The HD67029 is...

Страница 15: ...ut dip 1 ON like in figure The maximum length of the cable should be 1200m 4000 feet Here some codes of cables Belden p n 8132 2x 28AWG stranded twisted pairs conductor foil shield braid shield Belden...

Страница 16: ...ased by limiting the Baud rate and using fewer slaves but the bus voltage in the space state must at no point in a segment fall below 12V because of the remote powering of the slaves In the standard c...

Страница 17: ...that runs with Windows called SW67029 It is downloadable from the site www adfweb com and its operation is described in this document this manual is referenced to the last version of the software pre...

Страница 18: ...configuration A device s configuration can also be imported or exported To clone the configurations of a programmable M Bus master Modbus slave Converter in order to configure another device in the s...

Страница 19: ...hange the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is poss...

Страница 20: ...select HD67029 B2 The means of the fields for Modbus Slave are In the field Serial the serial port to use for the Modbus communication is defined In the field Baudrate the data rate of the Modbus line...

Страница 21: ...request only if a Modbus register is requested otherwise if Cyclic is checked the converter sends the request in M bus network cyclically In the field Delay for Cyclic s a time expressed in seconds i...

Страница 22: ...he Secondary Address from 0 to 99999999 of M Bus device In the field Node State it is possible to insert an address Modbus that contain the Status of the M Bus device If you don t need to know this pu...

Страница 23: ...or more information In the field Cut after it is possible to select after how many frames stops data requests It is used when the slave has got many data frames and you don t need to read all them In...

Страница 24: ...ary to select the type of data The field Dimension is used to select the dimension of the variable 8 16 24 32 32 real 48 64 bit Variable Length In the field Length Variable Len insert the length of th...

Страница 25: ...m BCD to Integer is checked the Converter converts the BCD value of variable in Integer format This happens only if the variable is in BCD format if it isn t nothing changes If the field Convert in Fl...

Страница 26: ...in the case of the dimension is Variable Length In the field Modbus Register it is necessary to insert the value of Modbus Register that contains the data of the M Bus device It is possible to insert...

Страница 27: ...registers as a 32 bit variables In the field Post Operation it is possible to define an operation on the data read before mapping them on Modbus registers In the field Position insert the number of th...

Страница 28: ...tatus 0x00 Signature Byte 2of2 0x00 Signature Byte 1of2 0x04 DIF 0x79 VIF Identification 0x00 Data Byte 4of4 0x00 Data Byte 3of4 0x00 Data Byte 2of4 0x00 Data Byte 1of4 0x04 DIF 0x06 VIF Energy 0x00 D...

Страница 29: ...t button of the mouse over an item Variable or Node it is possible to Copy Paste and Delete It is possible to Copy a variable from a Node and copy it to another Node or copy a Variable from a project...

Страница 30: ...h _Volume Flow m3 h _Volume Flow Ext m3 min _Volume Flow Ext m3 s _Mass Flow Kg h _Flow Temperature C _Return Temperature C _Temperature Difference K _External Temperature C _Pressure bar _Averaging...

Страница 31: ...Storage interval sec s day s _ Storage interval month s _ Storage interval year s _ Duration since last readout sec s day s _ Start date time of tariff _ Duration of tariff nn 01 11 min to day _ Peri...

Страница 32: ...ion of abs value only if negative contributions _ upper lower limit value _ of exceeds of lower upper limit _ Date time of begin end of first last lower upper limit exceed _ Duration of limit exceed _...

Страница 33: ...ber At the moment there are these possibilities None Type 1 Examples Identification Number Secondary Address 12345678 Address Register 1000 Convert BCD in Integer Identification Num not checked None T...

Страница 34: ...ays Operating Time coded like On Time Power 10 x 3 W 0 001 W to 10000 W Power 10 x J h 0 001 kJ h to 10000 kJ h Volume Flow 10 x 6 m3 h 0 001 l h to 10000 l h Volume Flow Ext 10 x 7 m3 min 0 0001 l mi...

Страница 35: ...Time Invalid 0 Valid 1 Invalid Summer Time 0 Standard Time 1 Summer Time Reserved 0 Data type G 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 2 15 2 14 2 13 2 12 2 11 21 0 2 9 2 8 Day 1 31 Month 1 12 Year 0 99 For...

Страница 36: ...s register 200 you have to compile the fields Manufacturer Specific Data Length MSD 1 241 and Offset MSD 0 240 in this way Manufacturer Specific Data 200 Length 10 Offset 0 On Modbus you will have thi...

Страница 37: ...se instructions Turn OFF the Device Connect the RS232 cable from your PC to the Converter Put Dip2 of Dip Switch A in ON position Select the COM port and press the Connect button Turn ON the device Ch...

Страница 38: ...nect the Ethernet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Devi...

Страница 39: ...PC Try to restart the PC Check the LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure tha...

Страница 40: ...the configurator software SW67029 It is possible to access to these functions by simple click on the button It has the following characteristics Possibility to scan M Bus network Automatic decode of M...

Страница 41: ...tronic Devices ADFweb com S r l User Manual M Bus master Modbus slave Converter Document code MN67029_ENG Revision 3 000 Page 41 of 47 MECHANICAL DIMENSIONS Figure 7a Mechanical dimensions scheme for...

Страница 42: ...rial Electronic Devices ADFweb com S r l User Manual M Bus master Modbus slave Converter Document code MN67029_ENG Revision 3 000 Page 42 of 47 Figure 7b Mechanical dimensions scheme for HD67029 B2 xx...

Страница 43: ...f 47 ORDERING INFORMATIONS The ordering part number is formed by a valid combination of the following HD67029 M xxx 20 Maximum number of slaves supported 20 up to 20 standard slaves 1 5mA consumption...

Страница 44: ...D67029 B2 232 40 M Bus master Modbus slave RS232 Converter up to 40 slaves connected to M Bus Order Code HD67029 B2 232 80 M Bus master Modbus slave RS232 Converter up to 80 slaves connected to M Bus...

Страница 45: ...ode APW040 Power Supply for M Bus Master device that supports up to 40 Slaves Order Code APW080 Power Supply for M Bus Master device that supports up to 80 Slaves Order Code APW160 Power Supply for M...

Страница 46: ...ollection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for th...

Страница 47: ...lease do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the prod...

Отзывы: