2.4. Configuring the SIGFOX SENSORS unit (analog input)
In this configuration, the device send a periodic data frame following the choosr setting. This mode is only available when the analog type
sensor are selected for both ways.
The SIGFOX SENSORS is configured via the combination of switches. The following settings can be changed:
•
Transmission interval
•
Inputs activation (sensors 1 and 2)
•
The type of sensor connected
CONFIGURATION TABLE:
Parameter
Value
SW1
SW2
SW3
SW4
SW5
SW6
Transmission frequency
(Only Available on
Analog Input Mode)
2 frames per day
OFF
OFF
50 frames per day
OFF
ON
100 frames per day
ON
OFF
140 frames per day
ON
ON
Activation of sensor
inputs
Sensors 1&2 inactives
OFF
OFF
Sensor 1 active
ON
OFF
Sensor 2 active
OFF
ON
Sensor 1&2 actives
ON
ON
Sensor type
Sensor 1&2 ANA
OFF
OFF
PLEASE NOTE
: You must set your switches before activating the meters. Once at least one way is activated and the SigFox SENSORS has been
started via magnet, the configuration with the switchs can no longer be possible.
If the configuration has any difference between the switchs and the product register value, the consistency error bit will be set to on in the
frame. This consistency verification is carried out every minute.
Содержание SIGFOX SENSORS
Страница 4: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 4 Page of 45 FR FRANCAIS...
Страница 6: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 6 Page of 45 FR...
Страница 25: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 25 Page of 45 GB ENGLISH...
Страница 27: ...SIGFOX SENSORS Mode d emploi User guide version V2 1 1 27 Page of 45 GB...