Frame description:
• Byte 2: Type of the sensor on channel A. Configured by the user (register 320).
• Bytes 3 to 5: Value measured on channel A.
• If the type of sensor is 0-10V: The value is expressed in µV
• If the type of sensor is 4-20mA: The value is expressed in nA
• Byte 6: Type of the sensor on channel B. Configured by the user (register 322).
• Bytes 7 to 9: Value measured on channel B.
• If the type of sensor is 0-10V: The value is expressed in µV
• If the type of sensor is 4-20mA: The value is expressed in nA
In the example in grey this gives:
• Byte 2=0x02: register 320, channel A configured for a 4-20mA sensor
• Bytes 3 to 5=0x0C3500=800,000 in decimal i.e. A value measured on channel A of: 800,000,x10=8,000,000nA i.e. 8mA
• Byte 6=0x01: register 322, channel B configured for a 0-10V sensor
• Bytes 7 to 9=0x4C4B40=5,000,000 in decimal i.e. a value measured on channel B of: 5,000,000 µV i.e. 5V
4.2.6 Summary of the conditions of the transmission of the uplink frames
The table below summarizes the conditions of the transmission of the different uplink frames:
Code
Description
Sending conditions
0x10
0x11
0x12
0x13
0x14
Product configuration data frames
• Start-up of the product
• Exit from the configuration mode (AT Command)
• Reception of a downlink frame 0x01
• Periodically if the inputs are disabled (period defined by the register 300)
0x20
Frames of information on the network
configuration
• Start-up of the product
• Exit from the configuration mode (AT Command)
• Reception of a downlink frame 0x02
0x30
Keep Alive frame
• Periodically in «event» mode
0x42
Data Frame
• Start-up of the product
• Event on an digital input configured in event mode
• Passing a threshold (event mode)
• The end of the period on input configured in periodic mode