Page 11
Manual SVL 4G Weblogger
Adesys B.V. | Wateringen
6 Appendices
6.1 Led status indication
Number of flashes for error (red)
1x
Problem with GSM module
2x
No SIM card detected
3x
Incorrect pin code
4x
PUK code necessary
5x
Power failure
6x
No SMS central number / no antenna level
7x
No telephone number coupled to input / 2G/4G connection cannot be
established / Ethernet error
8x
Connection to external server cannot be established
Number of flashes for network (orange)
Off
No antenna
Constant
Connected to external server
1x
Antenna level 1% < > 20%
2x
Antenna level 21% < > 40%
3x
Antenna level 41% < > 60%
4x
Antenna level 61% < > 80%
5x
Antenna level 81% < > 100%
Faster
Establishing connection (clientmode)
Number of flashes for on/busy (green)
Off
SVA is switched off
On
SVA is switched on
Faster
Starting up / sending message
1x
Input 1 active
2x
Input 2 active
3x
Input 3 active
4x
Input 4 active
5x
Input 5 active
6x
Input 6 active
7x
Input 7 active
8x
Input 8 active
System properties
SVL0000-I
Type of detector: (
a
larm dialler |) Web
l
ogger (|
m
odem)
Number of digital inputs
Number of GPIO inputs
Number of PT100 inputs
Number of relay outputs
I=4G variant
Input/output options (differs for each SVL model)
No.
Digital contact input (NO/NC)
4 - 8
Pulse counter
4 - 8
Digital voltage input (5-24V DC )
4 - 8
Analogue voltage input (0-10V DC)
4 - 8
Current input (0-20mA )
4 - 8
PT100 input (80-157Ω )
0 - 4
Open collector output
4 - 8
Relay output
0 - 2
7.2 Technical specifications