– 3 –
Local programming requires the use of a 2-line alpha keypad connected to the
keypad terminals on the control.
Field Function
[ ] = Default Value
Programmed Values
Field Function [ ] = Default Value Programmed Values
SYSTEM SETUP (
✱
20 –
✱
30)
✱
20 INSTALLER CODE
| | |
Enter 4 digits, 0–9 [4 1 1 2]
✱
21 QUICK ARM ENABLE
[0]
†
1 = enable: 0 = disable
✱
22 RF SYSTEM
[0]
†
0 = none; 1 = 5800 (5881/5882)
4 = 5800 w/ RF Jam Detection
✱
23 FORCED BYPASS
[0]
†
0 = none; 1 = bypass open zones
0 for UL installations.
✱
24 RF HOUSE ID CODE
[00]
|
00 = disable all wireless keypad usage;
01–31 = using 5827, 5827BD, and 5804BD
✱
25 WIRED ZONE EXPANSION
[0]
†
0 = none; 1 = 4219; 2 = 4229; 3 = 4204
✱
26 CHIME BY ZONE
[0]
†
0 = no; 1 = yes (program zones to chime
on zone list 3)
✱
27 X–10 HOUSE CODE
[0]
0 = A, 1 = B, 2 = C, 3 = D, 4 = E, 5 = F,
6 = G, 7 = H, 8 = I, 9 = J, # + 10 = K, # + 11 = L,
# + 12 = M, # + 13 = N, # + 14 = O, # + 15 = P
✱
28 PHONE MODULE ACCESS CODE
[00]
|
1st digit: enter 1–9; 2nd digit: enter # + 11 for
✱
,
or # + 12 for #.
Entering "0" for either digit disables code.
✱
29 OUTPUT TO LONG RANGE RADIO
[0]
0 = disable; enable = Trouble code 1–9, B (# +11),
C (# + 12), D (# + 13), E (# + 14), or F (# + 15).
The 2nd digit of Trouble Dialer Report is
automatically entered from field
✱
60. 0 for UL
installations.
✱
30 HARDWIRE SHORT DETECTION
[0]
†
1 = enable; 0 = disable
ZONE SOUNDS AND TIMING (
✱
31 –
✱
39)
✱
31 SINGLE ALARM SOUNDING/ZONE
[0]
†
1 = yes; 0 = no; 0 for UL installations.
✱
32 FIRE SOUNDER TIMEOUT
[0]
†
0 = timeout; 1 = no timeout
✱
33 ALARM BELL TIMEOUT
[1]
†
0 = none; 1 = 4 min; 2 = 8 min; 3 = 12 min;
4 = 16 min; 1 (4 min.) minimum for UL.
✱
34 EXIT DELAY (in seconds)
[2]
†
0 = 30
4 = 120
1 = 45
5 = 180
2 = 60
6 = 240
3 = 90
60 sec max for UL installations. Due to the Exit
Delay Restart feature, set for 30 seconds.
✱
35 ENTRY DELAY 1 (zone type 01)
[1]
†
0 = 30; 1 = 45; 2 = 60; 3 = 90; 4 = 120;
5 = 180; 6 = 240. 45 sec max. for UL installations.
✱
36 ENTRY DELAY 2 (zone type 02)
[2]
†
0 = 30; 1 = 45; 2 = 60; 3 = 90; 4 = 120;
5 = 180; 6 = 240. 45 sec max. for UL installations.
✱
37 AUDIBLE EXIT WARNING
[1]
†
0 = no; 1 = yes
✱
38 CONFIRMATION OF ARMING DING
[0]
†
0 = no; 1 = yes (wired keypads and RF);
2 = yes, RF only
✱
39 POWER UP IN PREVIOUS STATE
[1]
†
0 = no; 1 = yes; 1 for UL installations.
†
Entry of a number other than the one specified will give unpredictable results.