Question 22
O/C Zone
Enter the open/close reporting zone number, 1-4. A [0] entry
disables open/close reporting. If the zone selected was programmed
to be a pulse zone, (see Questions 8-11), this zone number selection
is invalid and will be tagged as an error.
Question 23
Telco Chan
Enter the physical Telco line fault zone, 1-4. A [0] entry disables
Telco detection. If this zone is the same as the open/close zone,
this selection will automatically be set to “0” and Telco
detection will be disabled. If the zone selected was programmed
to a pulse zone (see Questions 8-11) this zone number selection is
invalid and will be tagged as an error.
Question 24
Tamper zone
Enter tamper zone, 5-8. A [0] entry disables tamper detection. If
tamper is enabled, delayed restores will be automatically
generated.
Question 25
.
HS Ant. Tst (Y/N)
Press Y for 135 second interval antenna test. Press N if no antenna
test is desired.
Question 26
.
AC Loss RPT (Y/N)
If AC LOSS RPT is answered yes (Y), the radio will report the loss
of AC voltage within a 10 to 40 minute window, from its detection.
If this feature is disabled (N), this message will be suppressed.
NOTE: In either case, low battery messages will be sent as
detected.
Question 27
FLT REL ON (Y/N)
Press Y if fail-safe mode is desired. In this mode, the fault relay is
normally energized and will de-energize in the event of a radio
fault. Note that fail-safe mode draws slightly more standby
current. See the SETTING THE JUMPERS section for setting the
relay output.
Question 28
Flt Latched(Y/N)
Press Y if radio fault line is to be latched high upon detection of
transmission error. Press N if a momentary closure upon detection
of transmission error is desired.
REDUNDANT CENTRAL STATION REPORTING
Question 29
2
nd
CS (Y/N)
Press Y if redundant reporting to a second central station is
desired. Press N if not desired (skip to end).
Question 30
2CS Z1 (Y/N)
Press Y to enable reporting to second central station for
zone 1. Enter N to disable reporting.
Question 31
2CS Z2 (Y/N)
Press Y to enable reporting to second central station for
zone 2. Enter N to disable reporting.