No. 18: Battery Management Configurations 

Preliminary Operations: One device for all battery types. 
Completely  automatic,  all  devices  are  suitable  to  charge  most  batteries  types  thank  to  User  Selectable  charging 
curves.  They  can  charge  open  lead  acid,  sealed  lead  acid,  Gel  and  Ni-Cd.  It  is  possible  to  change  or  add  other 
charging curves connecting the device to a portable PC. 
Caution:Switch off the system before Setting the jumper.Only jumper in position 6 is Refreshed also with power ON. 
 

Don’t use Ni-Cd charging configuration in battery less than 7 Ah. 

 

 

 
Notice:  

1.  Do not leave the jumper in position 5; otherwise, in Backup mode, the battery discharges completely close to zero. 

This function permit to restart the device if the  

2.  Contact closed: Auxiliary LOAD enabled  

Contact open: Auxiliary LOAD disabled. 

This function permit to supply all electronic Load in Short Circuit, Over Load Protection.  
In this Way the device it is free to detect all parameters on the battery side.  

Battery Type Selection 

 

 

 

Jumper 

Position 

(Size 1) 

Jumper 

Position 

(Size 2) 

Jumper Position 

(Size 3) 

Dip Switch 

Position 

(Size 4) 

Float charge 

(Volt/Cell) 

Fast charge 

(Volt/Cell) 

Open 
Lead  

 

 

 

 

2.23 

2.40 

(AGM) Low 

 

 

 

 

2.25 

2.40 

Gel Battery 

 

 

 

 

2.30 

2.40 

NiCd  

 

 

 

 

1.4/cell 

(12V:10 cells) 
(24V:20 cells) 

 

1.5V/cell 

(12V:10 cells) 
(24V:20 cells) 

 

 
Li-Ion (4) 

 

 

 

 

 

 

3.45 

(12V:4 cells) 
(24V:8 cells) 

3.65 

(12V:4 cells) 
(24V:8 cells) 

Custom Charging 
Curve (5) 

 

 

 

 

Config. by DPY351 or 

ADELViewsystem. 

Functional Setting  

Function 

Battery Life test 
ON 

 

 

 

Jumper present or dip switch 
ON: Life test enabled (not for 
NiCd) 

Fast Charge 
Enable (3) 

 

 

 

Jumper present: Fast Charge 
enabled. It is possible remote 
Fast Charge enabling by 
RTCONN cable 

Power Supply 
Enabling 

 

 

 

 

Provide Power Supply 
Function On Battery Output 

“Start from 
Battery” (without 
Input Mains) (1) 

 

 

 

Switch ON the system without 
the “Mains In Vac”, only the 
battery is connected. For 
connection to external Push 
button use RTCONN cable 

Load Enabling 
(2)  

 

 

 

 

Present in CB122410A (Size4) 

 

  

 P

a

g

e

 7

 -

 C

h

a

p

te

r:

 

S

ta

n

d

a

rd

 a

n

d

 C

e

rt

if

ic

a

tio

n

s

 

 
 

Charging Curve 

Automatic  multi-stage  operation  and  real  time  diagnostic  allows  fast  recharge  and  recovery  of  deep  discharged 
batteries, adding value and reliability to the system hosting the CB device. The type of charging is Voltages stabilized 
and Current stabilized IUoUo. Five charging phases are identified by a flashing code on a Diagnosis LED. To maintain 
the  Output  Load  in  lower  Voltage  state,  don’t  put  jumper  in  position  6,  in  this  case  no  boost  charge  but  only  Float 
charge. Fast/Bulk Charge means also that every 288h, the device go in “Cycling Refresh Charging” for 85 minutes at 
2.4V/Cell.  

 

Standard and Certifications 

 

Electrical Safety For Mounting: 

Device  assembling:  UL508,  IEC/EN  60950  (VDE  0805)  and  EN  50178  (VDE  0160).  Installation  according:  IEC/EN 
60950. Input / Output separation: SELV EN 60950-1 and PELV EN 60204-1. Double or reinforced insulation. Safety of 
Electrical Equipment Machines: EN 60204-1. 

 In According to EMC 2014/30/UE and Low voltage directive 2014/35/UE 

EMC Standards

 

Immunity: 

EN 61000-4-2, EN 61000-4-3, EN 61000-6-2, EN 61000-4-4, EN 61000-4-5. 

EMC Standards Emission: 

EN 61000-6-4, EN 61000-6-3, EN 61000-3-2 (see data sheet for each device) 

Conformity to:  

EN60950 / UL60950-1 and CSA C22.2 No. 60950-1-07 (Information Technology Equipment) – Safety – Part1: General 
Requirement. 

 

IEC/EN 60335-2-29 Battery chargers 
Electrical safety EN54-4 Fire Detection and fire alarm systems;  
DIN41773 (Charging cycle) 

Approved:  

Devices:CB1210A, 
EN60950 / UL60950-1 and CSA C22.2 No. 60950-1-07 (Information Technology Equipment) – Safety – Part1: General 
Requirement. 

 

 

Rail Mounting: 

 
All modules must have a minimum vertical and horizontal distance of 10 cm to this power supply in order to 
guarantee  sufficient  auto  convection.  Depending  on  the  ambient  temperature  and  load  of  the  device,  the 
temperature of the housing can become very high. 

 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 

 

  

 P

a

g

e

 6

 -

 C

h

a

p

te

r:

 

B

a

tt

e

ry

 C

a

re

 

 
 

3.  Jumper present in Fast Charge means also that every 288h, the device go in “Cycling Refresh Charging”. This mode 

continue for 85 minutes at the same voltage condition: 2.4V/Cell; for Lead Acid Batteries. 

4.  Please note that it is possible to use lithium-charging curve just with a single BMS AND Only by custom request 
5.  By DPY351 or ADELViewsystem it is possible configure a Customized Charging Curve. After programming it is 

possible disconnect the programmer an use the device as standalone device. 

Battery Care 

The  Battery  Care  philosophy  is  base  on  algorithms  that  implement  rapid  and  automatic  charging,  battery  charge 
optimization  during  time,  flat  batteries  recovery  and  real  time  diagnostic  during  installation  and  operation.  The  Real 
Time  Auto-diagnostic  system, monitoring  battery faults  such  as,  elements  in  short  circuit,  accidental  reverse  polarity 
connection, disconnection of the battery, they can easily be detected and removed by help of Blink Code of Diagnosis 
Led; during the installation and after sell. Each device is suited for all battery types, by means of jumpers it is possible 
setting  predefined  curves  for  Open  Lead  Acid,  Sealed  Lead  Acid,  Gel,  Ni-Cd  and  Ni-Mh  (option).They  guarantees 
battery  reliability in  time  by  continuously  testing the  internal impedance  status,  avoids  any  possible  risk  of  damages 
and grants also a permanent, reliable and safe connection of the battery to the power supply. The system, through a 
battery  stimulation  circuit  with  algorithms  of  evaluation  of  the  detected  parameter,  is  able  to  recognize  sulphated 
batteries or batteries with a short-circuited element. 
Battery Test: Automatic. Every 60 sec. check battery connection. Every 220 minute in Float charge, make the test of 
the battery efficiency. The fault is signalized with relay commutation and diagnosis led blinking. 
 

Check for accidental disconnection of the battery cables: 

All In One detects accidental disconnection and immediately switched off the output power. 
 

Battery not connected: 

If the battery is not connected no output power. 
 

Test of quality wire connections: 

During Float charge the quality (resistance) on the battery connection is checked every 60 sec. This to detect if the 
cable connection has been properly made. 
 

Battery in Open Circuit or Sulphated: 

Every 220 minute. All In One tests of internal impedance, in Float charging mode. 

 
Reverse Polarity check: 

If the battery it is connected with inverted polarity, All In One is automatically protected. 
 

Test of battery voltage connections: 

Appropriate voltage check, to prevent connection of wrong battery types, more or less than the nominal voltage. 
 

End of Charge check

  

When the battery it is completely full, the device automatically switch in Float charging mode. 
 

Check for Battery Cells in short circuit  

Thanks to specific algorithms of evaluation, the CBs recognize batteries with cells in internal short circuit. 
In Float charge every 220 minute test of element in short circuit. 
 

Diagnosis of battery and device 

All  CB  devices  support  the  user  during  installation  and  operation.  A  Blink  code  of  Diagnosis  Led  allows  to 
discriminate among various possible faults. 
Error conditions, “LED Battery Fault” ON and “LED Diagnosis” blinking with sequence; see Display Signal section. 
 

Protection Features 

On  the  primary  side:

  the  device  is  equipped  whit  an  internally  fuse.  If  the  internal  fuse  is  activated,  it  is  most 

probable that there is a fault in the device. If happen, the device must be checked in the factory. 

On the secondary side Battery and load:

 The device is electrically protected against short circuits and overload. 

Inversion polarity:

 the module  it is  automatically  protected against  inversion of battery  polarity  and connection of 

load inverted. 

Over current and output short circuit: 

 the unit limits the output current (see the technical data). 

Deep discharge: 

not possible. The unit disconnects the battery when a minimum voltage level is reached. 

 

 

Thermal behaviour 

Surrounding  air  temperature  50°C.  For  ambient  temperature  of  over  50°C,  the  output  current must  be  reduced  by 
2.5%  per °C.  Max 70°C  At the  temperature of  70°C the output current  will be  50% of In. The equipment  does  not 
switch  off  in  case  of  ambient  temperature  above  70°C  or  thermal  overload.  The  devices  are  protected  for  Over 
temperature conditions “worst case”; in this situations the device Shut-down the output and automatic restart when 
temperature inside fall. 
 

 

  

 P

a

g

e

 8

 -

 C

h

a

p

te

r:

 

S

ta

n

d

a

rd

 a

n

d

 C

e

rt

if

ic

a

tio

n

s

 

 
 

 

CB 

 Charge & Testing

In pu t (V olt)

115  –  2 3 0  –  2 7 7 Va c

115  –  2 3 0  –  2 7 7 V a c

115  –  2 3 0  –  2 7 7 V a c

115  –  2 3 0  –  2 7 7 V a c

O u tp u t (V d c  – A – W)

12 V dc  –  3 5 A  –  4 8 0 W

2 4 Vdc  –  10 A  –  2 4 0 W

2 4 V dc  –  2 0 A  –  4 8 0 W 12 -2 4 V / 15 - 10 A / 2 8 0 W

Mo de l

C B 12 3 5 A

C B 2 4 10 A C

C B 2 4 2 0 A

C B 12 2 4 10 A

INP UT  DAT A

N o m ina l Input  Vo lt a ge

115 – 230 – 277Vac

115 – 230 – 277Vac

115 – 230 – 277Vac

115 – 230 – 277Vac

Input  Vo lt a ge  R a nge

  90 – 135Vac
180 – 305Vac

  90 – 135Vac
180 – 305Vac

  90 – 135Vac
180 – 305Vac

  90 – 305Vac

Inrus h C urre nt  ( Vn a nd In Lo a d)  I

2

t

 35 A  

 5msec

 16 A  

 5msec

 35 A 

 5msec

 16 A  

 5msec

F re que nc y

47 – 63 Hz ±6%

47 – 63 Hz ±6%

47 – 63 Hz ±6%

47 – 63 Hz ±6%

Input  C urre nt   ( 115  –  2 3 0 V a c )

8.0 – 4.2A

3.3 – 2.2A

8.0 – 4.2A

3.3 – 2.2A

Int e rna l F us e

10A

6.3A

10A

6.3A

E xt e rna l F us e  ( re c o m m e nde d)

16A

16A

16A

16A

O UT P U T D AT A

O ut put  Vdc  /  I

N

12Vdc – 35A

24Vdc – 10A

24Vdc – 20A

12Vdc 15A/24Vdc 10A

M inim um  lo a d

No

No

No

No

E ff ic ie nc y ( 5 0 % o f  In)

 91%

 88%

 91%

 91%

S ho rt -c irc uit  pro t e c tio n

Yes

Yes

Yes

Yes

O v e r Lo a d pro t e c tio n

Yes

Yes

Yes

Yes

O v e r V o lt a ge  O ut put  pro t e c tio n

Yes

Yes

Yes

Yes

R e v e rs e  ba t te ry pro te c t io n

Yes

Yes

Yes

Yes

D e t e c t io n o f  e le m e nt in s ho rt c irc uit

Yes

Yes

Yes

Yes

B A T T E R Y  C H A R G E R  O UT P UT  

B o o s t –  B ulk  c ha rge  ( T yp. a t  I

N

) ( 1)

14.4Vdc

28.8Vdc

28.8Vdc

28.8Vdc

M a x.T im e  B o o s t – B ulk  c ha rge  ( T yp. a t I

N

)

15h

15h

15h

15h

M in.T im e  B o o s t – B ulk  c ha rge  (T yp. a t  I

N

)

1min.

1min.

1min.

1min.

F lo a t  c ha rge  (T yp. a t  I

N

) ( 1)

13.75Vdc

27.5Vdc

27.5Vdc

27.5Vdc

R e c o v e ry C ha rge

2 – 9Vdc

2 – 18Vdc

2 – 18Vdc

2 – 10Vdc /2 – 20Vdc

S wit c hing o n a ft e r a pplying m a ins  v o lta ge

2.5sec.

E nd o f  c ha rging c urre nt  B ulk  -  A bs o rpt io n to  F lo a t

0.3A

S ta rt  up wit h c a pa c it iv e  lo a d

≤ 

30.000µF

R e s idua l R ipple

≤ 

60 mVpp

C ha rging m a x I

bat t

35A  ± 5%

10A  ± 5%

20A ± 5%

15A  ± 5% /20A  ± 5%

C ha rging c urre nt  Lim it ing I

N

 ( I

adj

)

Yes

Yes

Yes

Yes

Q uie s he nt  C urre nt

100mA

100mA

100mA

100mA

S IG N AL  O UT P UT  (RELA Y )

M a in o r B a c k up P o we r 

Yes

Yes

Yes

Yes

Lo w B a tt e ry a nd F a ult B a tt e ry 

Yes

Yes

Yes

Yes

M a in o r B a c k up -  F a ult B a tt e ry

No

No

No

Yes

AU X IL IARY  O UT P UT  (RJ 4 5  C O NNECT IO N) FO R :

T e m p. C ha rging pro be

Yes

Yes

Yes

Yes

V o lt a ge  dro p c o m pe ns a t io n

Yes

Yes

Yes

Yes

R e m o t e  m o nit o ring dis pla y

Yes

Yes

Yes

Yes

CL IMAT IC D AT A

A m bie nt  T e m pe ra t ure  o pe ra t io n

-30 ÷ +70°C

-30 ÷ +70°C

-30 ÷ +70°C

-25 ÷ +70°C

D e  ra t ing T ª > ( In)

> 50°  2.5% °C

> 50°  2.5% °C

> 50°  2.5% °C

> 50°  2.5% °C

A ut o m a tic  D e  ra t ing

No

No

No

No

A m bie nt  T e m pe ra t ure  St o ra ge

-40 – +85°C

-40 – +85°C

-40 – +85°C

-40 – +85°C

H um idit y a t  2 5  °C

 95% to  25°C

 95% to  25°C

 95% to  25°C

 95% to  25°C

G ENERAL  DA TA

Is o la tio n V o lt a ge  ( IN  /  O UT )

3000Vac

3000Vac

3000Vac

3000Vac

Is o la tio n V o lt a ge ( IN  /  P E )

1605Vac

1605Vac

1605Vac

1605Vac

Is o la tio n V o lt a ge ( O UT  /  P E )

500Vac

500Vac

500Vac

500Vac

P ro te c t io n C la s s  ( EN / IE C  6 0 5 2 9 )

IP 20

IP  20

IP  20

IP  20

R e lia bilit y ( M T B F  IE C  6 17 0 9 )

> 300 000 h

> 300 000 h

> 300 000 h

> 300 000 h

P o llut io n D e gre e  E nv iro nm e nt  

2

2

2

2

C o nne c t io n T e rm ina l B lo c k s  Sc re w T ype

4mm

2,5mm

4mm

2,5mm

P ro te c t io n c la s s   (wit h P E  c o nne c t e d)

D im e ns io n ( w- h- d)

150x115x135 mm

100x115x135 mm

150x115x135 mm

100x115x135 mm

We ight

1.5 kg appro x

0.85 kg appro x

1.5 kg appro x

0.85 kg appro x

S a fe t y S t a nda rd A ppro v a l

CE

CE

CE

CE

CO N NECT IO N DIA G RAM

(1) - Depend on jumper selection

www.adesystem.com