Technical data and limit values
MSX-E1516
www.addi-data.com 22
NOTICE!
The connection lines must be installed in such a way that they are
protected against mechanical loads.
5.3
Version
The Ethernet system
MSX-E1516
is available in the following versions:
Table 5-1: MSX-E1516: Versions
Version
Features
MSX-E1516
16 digital inputs/outputs, 24 V
MSX-E1516-NPN
16 digital inputs, 24 V (NPN)
The specific version name can be found on the type label of your Ethernet system (see also Chapter 1.1
of the general MSX-E manual).
5.4
Limit values
Height: 2000
m
over
NN
Operating temperature:
-40 °C to +85 °C
Storage temperature:
-40 °C to +85 °C
Relative air humidity
at indoor installation:
50 % at +40 °C
80 % at +31 °C
(Ice formation from condensation must be
prevented.)
Current supply:
Nominal voltage:
24 VDC
Supply voltage:
18-30 V
Current consumption (at 24 V):
200 mA ± 10 %
(when the outputs are switched off)
Safety:
Degree of protection:
IP 65
1
Optical isolation:
1000 V
Reverse polarity protection:
1 A max.
NOTICE!
After boot-up, the MSX-E system should warm up for a minimum
15 minutes so that a constant internal temperature will be
reached.
1 The degree of protection is only provided when the relevant protection caps are used.