background image

 

 

 

 

 

DIN EN ISO 9001:2008 certified

  

 

Edition: 02.02-03/2015

 

 

 

 

TECHNICAL

 

DESCRIPTION

 

MSX-E1516

 

Ethernet digital I/O system

 

 

 

   

 

 

 

 

 

 

 

 
 

 

 

 

 

 

 

Содержание MSX-E1516

Страница 1: ...DIN EN ISO 9001 2008 certified Edition 02 02 03 2015 TECHNICAL DESCRIPTION MSX E1516 Ethernet digital I O system ...

Страница 2: ... disclosure of this information for use by third parties is not permitted unless this right has been granted by the product licence issued Non compliance with this could lead to civil and criminal proceedings ADDI DATA software product licence Please read this licence carefully before using the standard software The customer is only granted the right to use this software if he she agrees with the ...

Страница 3: ...for it Observe the instructions of this manual Make sure that you do not forget or skip any step We are not liable for damages resulting from the wrong use of the Ethernet system Pay attention to the following symbols NOTICE Designates hints and other useful information NOTICE Designates a possibly dangerous situation If the instructions are ignored the Ethernet system the PC and or peripherals ma...

Страница 4: ...ion Digital inputs outputs 12 3 1 Pin assignment 12 3 2 LED display 13 3 3 Connection examples 13 3 3 1 Digital inputs 24 V 13 3 3 2 Digital outputs 24 V 14 3 4 Digital outputs 14 3 5 Watchdog 15 3 6 Event logic 15 3 7 Data format 17 4 Web interface Quick access to the MSX E system 18 4 1 I O Configuration 18 4 1 1 Menu item Digital I O 18 4 1 2 Menu item I O Watchdog 20 5 Technical data and limit...

Страница 5: ... Rearm 18 Fig 4 3 Digital I O Digital input filter configuration 18 Fig 4 4 Digital I O Digital Input Output events 19 Fig 4 5 Digital I O Digital Input Output latch event 19 Fig 4 6 I O Watchdog Current state 20 Fig 4 7 I O Watchdog Configuration 20 Fig 5 1 MSX E1516 Dimensions 21 Fig 5 2 MSX E1516 View from above 21 Tables Table 3 1 Pin assignment Digital inputs outputs 12 Table 3 2 LED display ...

Страница 6: ...ions 2 Brief description of the MSX E system functions features block diagram 3 Function description digital inputs outputs including pin assignment and connection examples 4 Description of the function specific pages of the MSX E web interface plus information on the data format 5 List of technical data and limit values of the MSX E system 6 Appendix with glossary and index 7 Contact and support ...

Страница 7: ... Directive 2006 95 EC 1 1 3 Limits of use All safety information and the instructions in the manuals must be followed to ensure proper intended use Uses of the Ethernet system beyond these specifications are considered as improper use The manufacturer is not liable for damages resulting from improper use The Ethernet system must remain in its anti static packaging until it is installed Please do n...

Страница 8: ... be opened It may only be opened by persons who have been authorised by ADDI DATA 1 3 User 1 3 1 Qualification Only persons trained in electronics are entitled to perform the following works Installation Commissioning Use Maintenance 1 3 2 Country specific regulations Do observe the country specific regulations regarding the prevention of accidents electrical and mechanical installations Electroma...

Страница 9: ... can send them to us by e mail or call us E mail info addi data com Phone 49 7229 1847 0 Manual and software download from the Internet The latest versions of the technical manual and the standard software for the Ethernet system MSX E1516 can be downloaded for free at www addi data com NOTICE Before using the Ethernet system and in case of malfunction during operation check if there is an update ...

Страница 10: ...ibrations dirt or extreme temperatures Moreover it can be used in the extended operating temperature range from 40 C to 85 C and is equipped with numerous protective circuits The Status LED provides for a quick and easy error diagnosis The electronics are no longer in the computer itself but in an external housing connected to the computer via Ethernet As the Ethernet system is attached in direct ...

Страница 11: ...Brief description MSX E1516 www addi data com 11 2 2 Block diagram Fig 2 1 MSX E1516 Block diagram ...

Страница 12: ...lable Table 3 1 Pin assignment Digital inputs outputs Cable black Pin No Female connector 5 pin M12 Lead colour 1 24 V output brown 2 Digital I O 2n 1 white 3 GND blue 4 Digital I O 2n black 5 not connected grey Please note that the female connector n is dual wired and that the digital I Os are determined via 2n 1 or 2n with 0 n 7 Examples Female connector 0 n 0 Pin 2 2 x 0 1 Digital I O 1 Pin 4 2...

Страница 13: ... No voltage applied Output active Lights red Output is active No voltage applied Caution risk of short circuit Input inactive Lights green Input is ready for operation Signals can be received Input active Lights yellow Input is active Signal is being received 3 3 Connection examples 3 3 1 Digital inputs 24 V Fig 3 1 Connection example Digital inputs 24 V www addi data com 13 ...

Страница 14: ...nly inputs or outputs can be configured In the event of a system reboot the configuration is only persistent if it has been changed on the web interface A port configured as an output is high impedance The status of the outputs can be read back by way of control If a short circuit occurs at a connected output this output will be deactivated As soon as the short circuit has been eliminated a rearm ...

Страница 15: ...state any write access to the outputs is ignored 4 To re enable write access the watchdog first has to be put in Stopped state web interface or deactivated by a software function To reactivate the watchdog it has to be put in Running state again or reinitialised and reactivated by a software function 3 6 Event logic The event logic function OR logic enables event datagrams to be generated when the...

Страница 16: ...35 μs When the filter is activated the digital inputs are internally set to 0 If they are externally switched to 24 V for example they will only be set to 1 again when the complete filter time has elapsed By configuring a digital output via the web interface all other information from the Digital I O page including filter value and event logic is transferred to the MSX E System as well and that at...

Страница 17: ...format has time stamp Time stamp in μs high if data format has time stamp Mask of the event source Bit 0 15 Status change of the channel has generated the event Bit 16 28 0 Bit 29 Event logic bit is set when the status of the channel changes Bit 30 Synchro trigger has generated the event Bit 31 Hardware trigger has generated the event The event may be generated by several sources at the same time ...

Страница 18: ...ems see PDF link 4 1 1 Menu item Digital I O Fig 4 1 Digital I O Channels On this page you can configure the digital channels as pairs of inputs or outputs For each output also the status 0 or 1 has to be defined Fig 4 2 Channels Rearm After a short circuit occurred the required rearm see Chapter 3 4 can be carried out via the correspondent button Fig 4 3 Digital I O Digital input filter configura...

Страница 19: ...ated In addition a time stamp can be set for each event The event logic is stopped via the corresponding button NOTICE Please read Chapter 3 6 if you have activated the digital input filter Fig 4 5 Digital I O Digital Input Output latch event The current status of the digital inputs or outputs can be saved via the synchro trigger and be sent via the data server A time stamp is available as an opti...

Страница 20: ...20 4 1 2 Menu item I O Watchdog Fig 4 6 I O Watchdog Current state On this page the current status of the watchdog for the digital inputs and outputs is displayed Fig 4 7 I O Watchdog Configuration You can configure the watchdog by defining the time unit and the watchdog time ...

Страница 21: ...fied EMC laboratory in accordance with the norm from the EN 61326 series IEC 61326 The limit values as set out by the European EMC directive for an industrial environment are complied with The respective EMC test report is available on request 5 2 Mechanical structure Fig 5 1 MSX E1516 Dimensions Dimensions L x W x H 215 x 110 x 50 mm Weight 900 g 960 g with MX Rail Fig 5 2 MSX E1516 View from abo...

Страница 22: ...eneral MSX E manual 5 4 Limit values Height 2000 m over NN Operating temperature 40 C to 85 C Storage temperature 40 C to 85 C Relative air humidity at indoor installation 50 at 40 C 80 at 31 C Ice formation from condensation must be prevented Current supply Nominal voltage 24 VDC Supply voltage 18 30 V Current consumption at 24 V 200 mA 10 when the outputs are switched off Safety Degree of protec...

Страница 23: ...0 30 V Input current 11 mA typ at nominal voltage Max input frequency 2 MHz at nominal voltage Logic input levels UHmax 30 V UHmin 19 V ULmax 14 V ULmin 0 V 5 V trigger input optional Number of inputs 1 Filter Protective circuit low pass transorb diode Optical isolation 1000 V via opto couplers Nominal voltage 5 VDC Input voltage 0 5 V Input current 12 mA typ at nominal voltage Max input frequency...

Страница 24: ...round according to IEC 1131 2 Nominal voltage 24 VDC Supply voltage 18 30 V Current 1 85 A max for each group2 via PTC Output current per output 500 mA max Short circuit current per output 1 7 A max shut down logic at 24 V RLoad 10 mΩ RDS ON resistance 280 mΩ max Switch on time 100 μs max RL 48 Ω of 80 Vout Switch off time 150 μs max RL 48 Ω of 10 Vout Overtemperature shut down 135 C max output dr...

Страница 25: ... and 1 Gbit s or 10 Gbit s Gigabit Ethernet This widely used technology for computer networking in a LAN has been standardised since 1985 IEEE 802 3 and ISO 8802 3 Ethernet technology is now common practice in the office environment After making even very tough real time requirements possible and adapting the device technology bus cables patch fields junction boxes to the harsh application conditi...

Страница 26: ...infinity the L level corresponds to digital 0 Limit value Exceeding the limit values even for a short time can easily result in the destruction of the component or the temporary loss of functionality MAC address MAC Media Access Control This is the hardware address of network components used to identify them uniquely within the network Optical isolation Optical isolation means that there is no flo...

Страница 27: ...e group of this protocol family Trigger A trigger is a pulse or signal for starting or stopping a special task Triggers are often used for controlling data acquisition UDP User Datagram Protocol This is a minimal connection free network protocol which is part of the transport layer within the Internet protocol family The purpose of UDPs is to ensure that data transmitted over the Internet reach th...

Страница 28: ... 21 EMC 21 Event logic 15 Functions 10 Glossary 25 Handling 9 Intended use 7 LED display Digital I O 13 Limit values 22 Pin assignment Digital I O 12 Safety precautions 7 Technical data 21 Update Driver 9 Firmware 9 Manual 9 Usage restrictions 7 User Qualification 8 Version 22 Watchdog 15 Web interface I O Configuration 18 www addi data com 28 ...