ADCP-80-531 • Issue 4 •July 2004
Page 15
© 2006, ADC Telecommunications, Inc.
Figure 7. Mounting Brackets for Mounting Circuit Breaker Panel
in 19- and 23-Inch (48.26 or 58.42 cm) Racks
1.21 Environmental Characteristics
lists the environmental characteristics of the PowerWorx Select Series circuit
breaker panel.
Table 2. PowerWorx Select Series Circuit Breaker Panel Environmental Characteristics
PARAMETER
DESCRIPTION
Operating temperature
–5° C to +55° C
Storage temperature
–45° C to +85° C
Humidity range
0% to 95% humidity (non-condensing)
Altitude range
–197 ft. (0.06 km) to 13,000 ft. (3.96 km) above sea level
Fire rating
All components UL94-V1
Earthquake design
NEBS Level 3, Zone 4
Acoustic noise
0 dBA above ambient
Heat dissipation (fully loaded) 50 watts @ 100 Amps per bus, 100 watts @ 200 Amps
total circuit breaker panel load
Heat dissipation (no load)
1 watt per bus
19-INCH RACK MOUNTING
BRACKET INSTALLATION
23-INCH RACK MOUNTING
BRACKET INSTALLATION
USE 3/8-INCH (9.525 MM) 12-24
THREAD-FORMING SCREWS AND
WASHERS TO SECURE MOUNTING
BRACKETS TO RACK
USE 5/16-INCH (7.936 MM) 8-32
THREAD-FORMING FLAT-HEAD
SCREWS TO SECURE MOUNTING
BRACKETS TO PANEL
16965-A