![ADC PG-PLUS PCU-796 Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/adc/pg-plus-pcu-796/pg-plus-pcu-796_manual_2847438016.webp)
LED Descriptions
SCP-PCU796-010-04H
6
June 24, 2003
PCU-796 List 1
LED D
ESCRIPTIONS
Figure 4 shows the PCU-796 front edge indicators.
One green POWER LED and four yellow CONDITIONER
LEDs are present. The POWER LED is green when the -48 V office battery and battery return are present at the
card edge pins. If fuse F1 blows, the POWER LED goes off and -48 V office battery is applied to the Fuse Alarm
pin on the card edge connector.
The yellow CONDITIONER LEDs go on when one or more of the conditioner circuits sense current flow on the
PGTC sleeve lead output (see Table 1).
Figure 4.
PCU-796
Unit
Table 1.
LED Indicators on Front Edge of the PCU-796
Indicator
Condition
Description
POWER
ON
PCU-796 is powered on.
OFF
PCU-796 is not receiving power.
CONDITIONER #1
ON
Conditioner circuit #1 is inactive.
OFF
Conditioner circuit #1 is active.
CONDITIONER #2
ON
Conditioner circuit #2 is inactive.
OFF
Conditioner circuit #2 is active.
CONDITIONER #3
ON
Conditioner circuit #3 is inactive.
OFF
Conditioner circuit #3 is active.
CONDITIONER #4
ON
Conditioner circuit #4 is inactive.
OFF
Conditioner circuit #4 is active.
Содержание PG-PLUS PCU-796
Страница 4: ...Inspecting Your Shipment SCP PCU796 010 04H June 24 2003 PCU 796 List 1 ...
Страница 6: ...SCP PCU796 010 04H ii June 24 2003 PCU 796 List 1 ...
Страница 8: ...SCP PCU796 010 04H iv June 24 2003 PCU 796 List 1 ...
Страница 10: ...SCP PCU796 010 04H vi June 24 2003 PCU 796 List 1 ...
Страница 23: ......