ADCP-50-304 • Issue 19 • June 1999 • Section 4: PatchSwitch X.21
Page 4-9
© 1999, ADC Telecommunications, Inc.
3.8
B Alarm Enable/Disable
The alarm can be disabled by moving the jumper labeled ALMB/ALMB on the module board.
The alarm is enabled when the jumper is in the ALMB position. The alarm is disabled when the
jumper is in the ALMB position.
3.9
PSM-832002 Module Quiescent State Indicators
Six LEDs located on the front panel indicate the presence of the quiescent states found in
. When the module is powered up and not connected to a X.21 circuit LED number
one will be on indicating a state one condition. This is like an idle state on a live X.21 circuit.
4
POWER REQUIREMENTS
The PatchSwitch chassis requires a power supply (110 Vac/60 Hz, 220 Vac/50 Hz, or –48 Vdc
input) to supply the modules with power. The power supply provides the correct dc output
voltage and current for the PatchSwitch chassis.
Table 4-3. B Alarm Time Delay Settings
ARC LENGTH
SWITCH POSITION
TIME DELAY
V
0
None
Shortest
1
55 msec
2
117 msec
3
242 msec
4
492 msec
5
992 msec
6
1.9 sec
Longest
7
3.9 sec
Table 4-4. Quiescent State Indicators
STATE
DTE
DCE
LED COLOR
1
Ready
Ready
Green
14
Controlled Not Ready
Ready
Red
18
Ready
Not Ready
Red
22
Uncontrolled Not Ready
Not Ready
Red
23
Controlled Not Ready
Not Ready
Red
24
Uncontrolled Not Ready
Ready
Red
Содержание and V35
Страница 10: ...INTRODUCTION...
Страница 20: ...FUNCTIONAL DESCRIPTION...
Страница 39: ...PATCHSWITCH V 35...
Страница 49: ...PATCHSWITCH X 21...
Страница 62: ...SITE PREPARATION...
Страница 64: ...ADCP 50 304 Issue 19 June 1999 Section 5 Site Preparation Page 5 2 1999 ADC Telecommunications Inc...
Страница 65: ...INSTALLATION...
Страница 75: ...OPERATION...
Страница 100: ...GENERAL INFORMATION...