American Dryer Corp.

112217 - 4

NOTE 1

Opening from combustible materials must be 2-inches (5.08 cm)
larger than the duct (all the way around).  The duct must be centered
within this opening.

NOTE 2

Distance should be 2 times the diameter of the duct to the nearest
obstruction.

A = 6-inches (15.24 cm)
B = 12 feet (3.66 meters)

NUMBER OF DRYERS

4

3

2

1

MINIMUM CROSS-

SECTIONAL AREA

SQ IN

164

120

80

54

SQ CM

1058

774.2

516.1

348.4

MINIMUM ROUND
DUCT DIAMETER

IN

14

12

10

8

CM

35.56

30.48

25.4

20.32

NOTE 1

Opening from combustible materials must be 2-inches (5.08 cm)
larger than the duct (all the way around).  The duct must be centered
within this opening.

NOTE 2

Distance should be 2 times the diameter of the duct to the nearest
obstruction.

A = 12 feet (3.66 meters)

B = 8-inches (20.32 cm)

The length of the ductwork from the dryer to the outside
exhaust outlet, must not exceed 12 feet (3.66 meters).  

The

minimum diameter of this ductwork must be at least
8-inches (20.32 cm) even though the dryer exhaust duct
connection is smaller

.  Including tumbler/dryer elbow

connections or elbows used for outside protection from the
weather, no more than 4 90° elbows should be used in the
exhaust duct run.  If more than the equivalent of four 90°
elbows are used, the cross-sectional area of the ductwork
must be increased.

Multiple Dryer (Common) Venting

IMPORTANT: 

For extended ductwork runs, the cross-

sectional area of the ductwork can only be increased to an
extent.  When the ductwork approaches the maximum
limits as noted in this manual, a professional HVAC firm
should be consulted for proper venting information.

If it is not feasible to provide separate exhaust ducts for
each dryer, ducts from individual dryers may be channeled
into a “common main duct.”  The individual ducts should
enter the bottom or side of the main duct at an angle not
more than 45º in the direction of airflow.  The main duct
should be tapered, with the diameter increasing before each
individual duct is added.  The minimum diameter of the
individual ductwork must be at least 8-inches (20.32 cm).

IMPORTANT: 

No more than four dryers should be

connected to one main common duct.

The illustration below shows the minimum cross-sectional
area for multiple dryer round or square venting.  These
figures must be increased if the main duct run from the last
dryer to where it exhausts to the outdoors is longer than 12
feet (3.66 meters) or has more than 1 elbow in it.

Multiple Dryer Venting with 6-Inch (15.24 cm) Diameter

440 cfm (12.46 cmm) Exhaust Connections at Common Duct

NOTE: 

When the exhaust ductwork passes through a wall,

ceiling, or roof made of combustible materials, the
opening must be 2-inches (5.08 cm) larger than the duct
(all the way around).  The duct must be centered within
this opening.
As per the National Fuel Gas Code, “Exhaust ducts for
type 2 clothes dryers shall be constructed of sheet metal
or other noncombustible material.  Such ducts shall be
equivalent in strength and corrosion resistance to ducts
made of galvanized sheet steel not less than 26 gauge
(0.0195-inches [0.50 mm]) thick.”

The ductwork for this appliance must be suitable for the
appliance category in accordance with national installation
regulations of the country of destination.

Outside Ductwork Protection

To protect the outside end of the horizontal ductwork from
the weather, a 90° elbow bent downward should be installed
where the exhaust exits the building.  If the ductwork travels
vertically up through the roof, it should be protected from the
weather by using a 180° turn to point the opening downward.
In either case, allow at least twice the diameter of the duct
between the duct opening and the nearest obstruction (refer
to the diagram).

IMPORTANT: 

Do not use screens, louvers, or caps on the

outside opening of the exhaust ductwork.

Single Dryer Venting

IMPORTANT: 

For extended ductwork runs, the cross-

sectional area of the ductwork can only be increased to an
extent.  When the ductwork approaches the maximum
limits as noted in this manual, a professional HVAC firm
should be consulted for proper venting information.

Содержание AD222

Страница 1: ...n et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz WARNING For your safety the information in this manual must be followed to minimize the risk of fire or explosion and to prevent property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appl...

Страница 2: ...r order is processed accurately and promptly These instructions are only valid if the following country code is on the appliance If this code is not present on the appliance it is necessary to refer to the technical instructions which will provide the necessary information concerning the modification of the appliance to the condition of use for the country In accordance with EN ISO 3166 1 the name...

Страница 3: ... that the local distribution conditions nature of gas and pressure and adjustment of the appliances are compatible CAUTION Dryer s should never be left unattended while in operation Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper operation Attention Au moment de l entretien des commandes étiquetez tous les fils avant de les débrancher Des err...

Страница 4: ...l constitute a fire hazard and should not be placed in a tumble dryer Do not dry mop heads Contamination by wax or flammable solvents will create a fire hazard WARNING Do not use heat for drying articles that contain plastic foam sponge rubber or similarly textured rubber materials Drying in a heated tumbler may damage plastics or rubber and also may be a fire hazard The possible presence of resid...

Страница 5: ...________________________________ ____________________________________________________________ IMPORTANT The dryer must be installed in a location environment which the ambient temperature remains between 40 F 4 44 C and 130 F 54 44 C The operation of this appliance may affect the operation of other types of gas appliances which take their air for safe combustion from the same room If in doubt cons...

Страница 6: ...MPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION PER POCKET 3 8 M N P T VOLTAGE AVAILABLE 208 240V 1ø 50 60 Hz APPROXIMATE NET WEIGHT 302 lb 136 98 kg APPROXIMATE SHIPPING WEIGHT 342 lb 155 12 kg AIRFLOW PER POCKET 220 cfm 6 23 cmm EXHAUST CONNECTION DIAMETER PER POCKET 4 10 16 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE PER POCKET kW Btu hr kcal...

Страница 7: ...dclaundry com 7 Specifications _____________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Страница 8: ...fer to Exhaust Requirements section The dryer must be located in an area where correct exhaust venting can be achieved as noted in this manual refer to Exhaust Requirements section IMPORTANT The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be installed with adequate clearance for air openings into the combustion chamber CAUTION This dryer produ...

Страница 9: ... be made for remote or constricting passageways or where dryers are located at high altitudes or predominantly low pressure areas IMPORTANT Make up air must be free of dry cleaning solvent fumes Make up air that is contaminated by dry cleaning solvent fumes will result in irreparable damage to the motors and other dryer components NOTE Component failure due to dry cleaning solvent fumes will void ...

Страница 10: ...efore each individual duct is added The minimum diameter of the individual ductwork must be at least 8 inches 20 32 cm IMPORTANT No more than four dryers should be connected to one main common duct The illustration below shows the minimum cross sectional area for multiple dryer round or square venting These figures must be increased if the main duct run from the last dryer to where it exhausts to ...

Страница 11: ...s of the data label exactly The wire size must be properly sized to handle the related current WARNING 208 VAC and 230 240 VAC are not the same Any damage done to dryer components due to improper voltage connections will automatically void the warranty TERM LINE VOLTAGE 50 Hz 60 Hz HIGH 260 226 283 249 MED 239 208 260 230 LOW 217 189 236 208 Electrical Service Specifications Gas Models Only Check ...

Страница 12: ... 16 20 240 3ø 3 5 4 16 20 230 3ø 3 5 17 30 240 3ø 3 5 4 17 30 380 3ø 4 4 5 11 15 400 3ø 4 5 11 15 416 3ø 4 5 4 11 15 If local codes permit power to the dryer can be made by the use of a flexible UL listed power cord pigtail wire size must conform to rating of dryer or the dryer can be hard wired directly to the service breaker panel In both cases a strain relief must be installed where the wiring ...

Страница 13: ... for the appliance category in accordance with national installation regulations of the country of destination and if in doubt the installer must contact the supplier The manufacturer of this appliance does not recommend the use of flexible gas supply line hose An external gas supply shutoff must be provided WARNING CE Dryers Only This appliance must only be operated with the gas type indicated on...

Страница 14: ...Injector Data For Non CE European and Non AGA Australia Models Only Shaded areas are stated in metric equivalents Gas valve s internal regulator disabled Information is per pocket tumbler Consult factory for elevations over 2 000 feet 610 meters for correct orifice size Parts Required for Conversion Description ADC P N Qty Unregulated Gas Conversion Kit 140414 2 OR Regulated L P Gas Conversion Kit...

Страница 15: ... power to the dryer Close all shutoff valves for both top and bottom tumbler in dryer s gas supply line IMPORTANT The following procedures must be performed on both top and bottom tumblers Open the panels located just below each loading door Locate the gas train and disconnect the union three electrical plugs and the gas train mounting screws from the burner Carefully slide the gas train out of th...

Страница 16: ...refer to Gas Pressure Adjustment on this page Once test is complete turn gas cock to OFF position Remove manometer Tighten screw inside the pressure tap or install plug Turn gas cock to ON position and check for leaks with soap solution with main burner ON Preparation for Operation Start Up__ The following items should be checked before attempting to operate the dryer Read all CAUTION WARNING and ...

Страница 17: ...he remaining time NOTE The dryer can be stopped at any time by opening the main door or the lint door When the programmed drying time has expired the non coin microprocessor controller computer will proceed into the Cool Down Cycle Shutdown Instructions _______________ If the dryer is to be shutdown taken out of service for a period of time the following must be performed Discontinue power to the ...

Страница 18: ...f delivery can be obtained by the sender Shipping charges are not the responsibility of ADC All returns should be prepaid to the factory Any C O D or COLLECT returns will not be accepted IMPORTANT No replacements credits or refunds will be issued if the claim cannot be processed due to insufficient information The party filing the claim will be notified in writing either by FAX or CERTIFIED MAIL R...

Страница 19: ...e cleaning of appliances is recommended 7 Days After Installation and Every 12 Months Thereafter A competent professional should inspect bolts nuts screws setscrews grounding connections and nonpermanent gas connections unions shutoff valves and orifices Belts should be examined Cracked or seriously frayed belts should be replaced Complete an operational check of controls and valves Complete an op...

Страница 20: ...ADC Part No 112217 4 05 05 15 ...

Отзывы: