ADG-120DR MULTIPLE DRYER VENTING

ADG-120DR 12-INCHES (30.48 CM) DIAMETER (1,750 CFM [49.6 CMM])

EXHAUST CONNECTIONS AT COMMON DUCT

AD-120ES and ADG-120DR

Multiple Dryer (Common) Venting

If it is not feasible to provide separate exhaust ducts
for each dryer, ducts from individual dryers may be
channeled into a “common main duct.”  The
individual ducts should enter the bottom or side of
the main duct at an angle not more than 45° in the
direction of airflow and should be spaced at least
48-3/4” (123.83 cm) apart.  The main duct should
be tapered, with the diameter increasing before
each individual dryer branch duct is added.

IMPORTANT:

 No more than four dryers should be

connected to one main common duct.

The main duct may be any shape or cross-sectional
area, as long as the minimum cross section area is
provided.  The illustrations on the right show the
minimum cross section area for multiple dryer round
or square venting.  These figures must be increased
10 square inches (64.51 square centimeters) when
rectangular main ducting is used, and the ratio of
duct width to depth should not be greater than
3-1/2 to 1.  These figures must be increased in
proportion if the main duct run to the last dryer to
where it exhausts to the outdoors is unusually long
(over 20 feet [6.09 meters]) or has numerous elbows
(more than two) in it.  In calculating ductwork size,
the cross section area of a square or rectangular
duct must be increased twenty percent for each
additional 20 feet (6.09 meters).  The diameter of a
round exhaust must be increased ten percent for
each additional 20 feet (6.09 meters).  Each 90°
elbow is equivalent to an additional 15 feet (4.57
meters).

IMPORTANT:

 Exhaust back pressure measured by

a manometer at each dryer exhaust duct area must
be no less than 0 and must not exceed 0.3 in WC
(0.75 mb, 75 Pa).
For extended ductwork runs, the cross section area
of the ductwork can only be increased to an extent.
Maximum proportional ductwork runs cannot
exceed 20 feet (6.09 meters) more than the original
limitations of 20 feet (6.09 meters) with two elbows.
When the ductwork approaches the maximum limits
as noted in this manual, a professional HVAC firm
should be consulted for proper venting information.

The duct should be smooth inside with no
projections from sheet metal screws or other
obstructions, which will collect lint.  When adding
ducts, the duct to be added should overlap the duct
to which it is to be connected.  All ductwork joints
must be taped to prevent moisture and lint from
escaping into the building.  Inspection doors should
be installed at strategic points in the exhaust
ductwork for periodic inspection and cleaning of lint
from the ductwork.

NOTE:

 When the exhaust ductwork passes through

a wall, ceiling, or roof made of combustible
materials, the opening must be 2-inches (5.08 cm)
larger than the duct (all the way around).  The duct
must be centered within this opening.

To protect the outside end of the horizontal ductwork from the weather,
a 90° elbow bent downward should be installed where the exhaust
exits the building.  If the exhaust ductwork travels vertically up through
the roof, it should be protected from the weather by using a 180° turn
to point the opening downward.  In either case, allow at least twice the
diameter of the duct between the duct opening and nearest obstruction.

IMPORTANT:

 Do not use screens, louvers, or caps on the outside

opening of the exhaust ductwork.

AD-120ES MULTIPLE DRYER VENTING

14-INCHES (35.56 CM) DIAMETER, 2,150 CFM (60.88 CMM)

EXHAUST CONNECTION AT COMMON DUCT

(GAS, ELECTRIC, AND STEAM MODELS)

Содержание AD-120ES

Страница 1: ...ez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incendie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort Ne pas entre...

Страница 2: ...___________________________________________ ____________________________________________________________________________________________________ Replacement parts can be obtained from your reseller or...

Страница 3: ...brancher Des erreurs de c blage peuvent entra ner un fonctionnement inad quat et dangereux WARNING Children should not be allowed to play on or near the dryer s Children should be supervised if near...

Страница 4: ...perate dryer according to this manual and operator s manuals included with dryer may result in conditions which can cause serious injury death and or property damage Safety Precautions _______________...

Страница 5: ...anufacturer s Use this dryer only for its intended purpose drying fabrics The Cool Down Cycle of tumble dryers should be used to reduce the temperature of the items They should not be removed from the...

Страница 6: ...1 791 cfm 50 71 cmm EXHAUST CONNECTION DIAMETER 14 35 56 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A OVEN SIZE kW Btu hr kcal hr 72 245 700 61 900 75 6 258 000 65 000 VOLTAGE AVAILABLE...

Страница 7: ...dclaundry com 7 AD 120ES Specifications __________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice...

Страница 8: ...nufacturer reserves the right to make changes in specifications at any time without notice or obligation AD 120ES Specifications __________________________________________________________ WITH OPTIONA...

Страница 9: ...OW 1 750 cfm 49 55 cmm HEAT INPUT 300 000 Btu hr 75 599 kcal hr EXHAUST CONNECTION DIAMETER 12 30 48 cm COMPRESSED AIR CONNECTION N A COMPRESSED AIR VOLUME N A INLET PIPE CONNECTION 3 4 M N P T VOLTAG...

Страница 10: ...er Corp 113386 28 ADG 120DR Specifications ________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notic...

Страница 11: ...N or in Canada the installation must conform to applicable Canadian Standards CAN CGA B149 1 M91 Natural Gas or CAN CGA B149 2 M91 L P Gas or LATEST EDITION for General Installation and Gas Plumbing T...

Страница 12: ...re the exhaust transition piece to the dryer NOTE It is recommended that this joint be taped as well as all other duct joints to prevent moisture and lint from escaping into the building Dryer Enclosu...

Страница 13: ...the area must be increased by approximately thirty three percent Make up air openings should not be located in an area directly near where exhaust vents exit the building It is not necessary to have...

Страница 14: ...RTANT Exhaust back pressure measured by a manometer at the dryer exhaust duct area must be no less than 0 and must not exceed 0 3 in WC 0 75 mb 75 Pa NOTE When the exhaust ductwork passes through a wa...

Страница 15: ...l ductwork should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint When adding ducts the duct to be added should overlap the duct to which it...

Страница 16: ...T Exhaust back pressure measured by a manometer at each dryer exhaust duct area must be no less than 0 and must not exceed 0 3 in WC 0 75 mb 75 Pa For extended ductwork runs the cross section area of...

Страница 17: ...me without notice or obligation Electrical Service Specifications 3 Wire is available 12 8 14 3 Wire is available 12 8 14 Electric Reversing ELECTRICAL SERVICE SPECIFICATIONS PER DRYER IMPORTANT NOTES...

Страница 18: ...ty and any other relevant statutory regulations It is important that gas pressure regulators meet applicable pressure requirements and that gas meters be rated for the total amount of all the applianc...

Страница 19: ...dryer must be connected to the type of heat gas indicated on the dryer data label If this information does not agree with the type of gas available do not operate the dryer Contact the reseller who so...

Страница 20: ...P T 1 B S P T for CE and AGA dryers inlet pipe connection extending out the back area of the burner box The minimum pipe size connection supply line to the dryer is 1 1 4 diameter For ease of servicin...

Страница 21: ...ns made by a qualified professional to ensure that the installation is adequate and conforms to local and state regulations or codes IMPORTANT Failure to comply with the requirements stipulated in thi...

Страница 22: ...damage to the steam coil due to the overhung weight of the steam solenoid valve The supply and return line should be insulated This will save energy and provide safety for the operator and maintenanc...

Страница 23: ...ections will void warranty If the rear area of the dryer or the water supply is located in an area where it will be exposed to cold freezing temperatures provisions must be made to protect these water...

Страница 24: ...a coupling must be used to provide the minimum 1 2 supply feed line If the rear area of the dryer or the water supply is located in an area where it will be exposed to cold freezing temperatures prov...

Страница 25: ...________________________ _________________________________________________________________________________________________________________________________ _____________________________________________...

Страница 26: ...kPa L P Gas 10 5 in WC 26 1 mb 2 61 kPa IMPORTANT There is no regulator provided in an L P dryer The water column pressure must be regulated at the source L P tank or an external regulator must be ad...

Страница 27: ...Once the Cool Down Cycle begins at the end of the heat cycle the L E D display will read COOL DOWN TEMP ___ ___ MINUTES REMAINING At the end of the heat cycle the dryer will shut off the heat and con...

Страница 28: ...y is handled in an expeditious manner Parts Replacement parts should be purchased from the reseller from whom the equipment was purchased If the reseller cannot be contacted or is unknown contact the...

Страница 29: ...espondence pertaining to the returned part s must be included inside the package with the failed merchandise Each part must be tagged with the following information Model number and serial number of t...

Страница 30: ...e damper to bind or stick A back draft damper that is sticking partially closed can result in slow drying and shutdown of the heat circuit safety switches or thermostats If the hi limit trips due to a...

Страница 31: ...icator dots in the microprocessor controller computer L E D display are on Refer to the illustration below Procedure for Functional Check of Replacement Components ________ Phase 7 Microprocessor Cont...

Страница 32: ...l the drum temperature has dropped below 100 F 38 C The clear stop button on the Phase 7 keypad must be pressed to clear the error condition The open burner hi limit must be reset manually prior to th...

Страница 33: ...IL SWITCH CLOSED FAULT Sail switch is closed should be open at the start of a cycle O O O SAIL SWITCH OPEN FAULT Sail switch remained open after the cycle started Should have closed BURNER HIGH LIMIT...

Страница 34: ...ADC Part No 113386 28 02 05 15...

Отзывы: