Power and Grounding
150-204-100-03, Issue 3
10
May 7, 1999
HRE-204 List 1 and List 2
The non-isolated mode only uses one power supply, but has no failsafe feature, since all circuits are lost if the
power supply fails. To connect a single power supply for non-isolated mode:
1
Connect the power supply to either TB3 or TB4.
2
Connect the equivalent pins of the unused terminal block to the active terminal block. This connects the power
source to all slots.
Figure 8.
TB3 and TB4 Pin Assignments
Third party wall mount power supplies can be used to provide 48 V power for various plug applications, as shown
in
* Minimum input power lead wire size current capacity is based on 1000 circular mils per ampere.
Table 2.
Power Requirements for Various Plug Applications
HiGain Unit
Maximum
power
per unit
Number
of units
Power
Required
(mA)
Power supply
Input Power
AWG Wire Size*
(Two Inputs) (One Input)
HRU-402
3.5 Watts
1
73
Westell 6048-01 (100 ma)
26
26
1, 2, or 3
210
Teltrend 2005 (250 ma)
26
26
4
300
Troncom WPS-4806 (520 ma) 26
26
HRU-412
6 Watts
1
125
Teltrend 2005
26
26
2
250
Troncom WPS-4806
26
26
HLU-431 (no
doublers)
14 Watts
1
2
300
600
Troncom WPS-4806
Troncom WPS-4810
26
26
26
22
HLU-431
(with
doublers)
24 Watts
1
2
500
1000
Troncom WPS-4806
Troncom WPS-4810
26
22
22
20