Operation
2009 ADB Airfield Solutions, Incorporated
96A0288T
4-2
All rights reserved
Issued 9/04
Table 4-1 Output Current from Rotary Switch (3-Step/6.6A)
If you set the rotary switch to
the following...
The result is...
B10
4.8 A current output
B30
5.5 A current output
B100
6.6 A current output
Table 4-2 Output Current from Rotary Switch (5-Step/6.6 A)
If you set the rotary switch to
the following...
The result is...
B1
2.8 A current output
B2
3.4 A current output
B3
4.1 A current output
B4
5.2 A current output
B5
6.6 A current output
Table 4-3 Output Current from Rotary Switch (5-Step/20 A)
If you set the rotary switch to
the following...
The result is...
B1
8.5 A current output
B2
10.3 A current output
B3
12.4 A current output
B4
15.8 A current output
B5
20 A current output
See Figure 4-1. Refer to Table 4-4 for instructions on how to set up and use
remote control.
Table 4-4 Remote Control
If...
Then...
The rotary switch is set to position
REM and remote control wiring is
connected to remote control
terminal block TB1 on the
regulator
Remote control of the regulator is
possible.
The output current of the regulator
will correspond to the brightness
setting energized by remote 120 Vac
control signals.
Switch is set to OFF
Remote control signals will not
operate the regulator; that is, turn
the regulator on to a particular
brightness setting or turn the
regulator off.
No remote control connections
exist on terminal block TB1
(switch is set to REM)
The position REM becomes an
additional OFF position; that is, the
regulator is de-energized.
Local Control
(contd.)
Remote Control