Ferroresonant L-828/L-829 CCR
Description
2009 ADB Airfield Solutions, Incorporated
96A0288T
2-6
All rights reserved
Issued 9/04
The L-829 CCR monitoring options include the Insulation Resistance
Monitoring System (IRMS), Scanning Monitor Interface (SMI), and
Scanning Monitor Ready (SMR).
The IRMS is used only on the L-829. It performs scheduled cable
insulation resistance measurements and can also perform manually
requested measurements. IRMS provides the ability for monitoring the
long-term degradation of the airfield series circuit cabling and showing the
results on the L-829 CCR front display panel.
WARNING:
When servicing a regulator equipped with an
IRMS module, be sure that power to the IRMS is disconnected
before touching the IRMS board, or any of
the high voltage components or wires.
The scanning monitor interface is a relay assembly that can be mounted
internally to the front panel of the CCR. The relay assembly consists of
four relays and sockets. The relay assembly is used to generate feedback
signals concerning the CCRs operation to the Remote Multiplexer. The
relay assembly generates feed back for the following signals: Remote/local
status, commanded ON status, regulator running status, and primary power
status.
The scanning monitor ready includes the scanning monitor interface plus
one current transformer (CT) and one potential transformer (PT). It also
has resistor loads, and a fuse in the potential transformer secondary.
Differential signals presenting the actual series circuit voltage and current
are transmitted to the scanning monitor system two-conductor shielded
cables.
The series cutout Type SCO is often used at airports having a large number
of series circuits to isolate the series circuit from the CCR during
maintenance or testing operations. It also allows manual measurement of
resistance of the series circuit to ground without disconnecting the series
cable. The SCO cutout has a nominal working voltage of 5 kV and a
nominal carrying current capacity of 20 amps AC.
5.
L-828/L-829 CCR
Monitoring Options
Optional Insulation
Resistance Monitoring System
Optional Scanning Monitor
Interface
Optional Scanning Monitor
Ready
Optional Series Cutout Type
SCO