Recommended Procedure of Module Connection
1. Disassembly of the terminal connector covers.
Remove the terminal connector covers of the modules by means of a suitable tool.
Fig. Removal of the terminal connector covers
2. Break the interconnection of terminal connectors 485-B and 485-AR at the set end module (3600-
COM).
Fig. Interconnection at the end module 3600-COM
At the end module of the set (in this case 3600-COM) there is a resistance termination of RS-485 via
an interconnection of terminal connectors 485-B and 485-AR. This interconnection must be removed
and installed at the end module of the extended set (in this case 3600-MPX).
3. Interconnection of supply terminal connectors (VCC and GND).
The supply conductors are identified by the following colours
in the supplied set:
-
red, positive pole of the supply (+5 V, VCC)
-
blue, negative pole of the supply (GND).
Pay attention to the correct polarity of the supply voltage! The positive voltage is always at the
first terminal connector on the left.
remove
interconnection