background image

6.

4th stage indicator

7.

High temperature overheat indicator

8.

Manual reset high limit thermostat

9.

Control thermostat

Control Panel

1.

Thermometer

2.

On/off switch

3.

1st stage indicator

4.

2nd stage indicator

5.

3rd stage indicator

High efficiency electric boilers

39

Technical Data

TER 57

TER 86

TER 115

TER 144

TER 201

TER 259

Maximum output

kW

57.6

86.4

115.2

144

201.6

259.2

Nominal supply 

V

3 x 400 + N

Nominal supply (total)

amps

250.5

376

501

626

876.5

1127

Nominal supply (per phase)

amps

83.5

125.3

167

209

292

376

Dual heating elements*

#

12

18

24

30

42

54

Total capacity

L

155

155

155

155

250

250

Primary connection (female BSP) 

Ø

2"

2"

2"

2"

DN100

DN100

Weight empty

Kg

102

102

102

102

195

195

Weight full

Kg

257

257

257

257

445

445

Maximum operating temperature

°C

90

90

90

90

90

90

Heating element type

2 x 2.4

2 x 2.4

2 x 2.4

2 x 2.4

2 x 2.4

2 x 2.4

Maximum operating pressure  Primary: 4 bar

*A dual element consists of a single flange with a combined output of 4.8kW at 230 volts.

1

2

3 4

5 6 7

8

9

2

9

8

1

7

4

5

6

3

1.

Control panel

2.

Power cable entry position

3.

Power cable connections

4.

Control circuit terminals

5.

Power stage delay timer

6.

Element supply contactors

7.

Stove enamelled metal casing

8.

Heating elements

9.

Rigid polyurethane foam 

insulation

TER 57

TER 86

TER 115

TER 144

TER 201

TER 259

A

80mm

80mm 80mm 80mm

80mm 80mm 

B

124mm

124mm 124mm 124mm 190mm 190mm 

C

1134mm 1134mm

1134mm 1134mm 1060mm 1060mm

D

130mm 130mm 130mm 130mm 197mm 197mm

E

610mm 610mm 610mm

610mm 752mm 752mm

F

1380mm 1380mm 1380mm 1380mm 1380mm 1380mm

G

610mm 610mm 610mm 610mm 752mm 752mm

Characteristics

Dimensions