en
9
EN
FR
NL
ES
IT
DE
PL
RU
Smart Line SLE - SLE Plus
: 661Y2100 • A
TECHNICAL CHARACTERISTICS
DOMESTIC HOT WATER PERFORMANCES
DHW performance :
Heating source = External boiler
connected to tank *
SLE
130
SLE
160
SLE /
SLE Plus
210
SLE /
SLE Plus
240
SLE /
SLE Plus
300
Peak flow at
40°C [∆T = 30K]
L/10'
236
321
406
547
800
60°C [∆T = 50K]
L/10'
117
161
209
272
370
Constant flow at
40°C [∆T = 30K]
L/h
658
890
1132
1527
2100
60°C [∆T = 50K]
L/h
320
465
576
769
970
Peak flow 1
st
hour at
40°C [∆T = 30K]
L/60'
784
1063
1349
1820
2360
60°C [∆T = 50K]
L/60'
384
549
689
913
1100
Maximum absorbed power
kW
23
31
39
53
68
Reheat time
Minutes
22
22
20
20
22
* Conditions
: Primary circuit temperature : 85°C, water intake temperature : 10°C
MAXIMUM OPERATING CONDITIONS
Maximum Service Pressure [tank full of water]
- Primary circuit : .................................................3 bar
- DHW water circuit : ......................................8,6 bar
Maximum Temperature
- Maximum DHW temperature : ....................90°C
Supply Pressure (DHW circuit)
- Max. 6 bar without requiring a pressure reducing valve
Water Quality
- Chlorides < 150 mg/L
- 6 ≤ pH ≤ 8
- If the water hardness is > 20°fH, the installation of a water softener is recommended.