1. For the North Switch, program Button 1 to ON MODE for Relay 1 and Relay 2.
Program Button 2 to OFF MODE for Relay 1 and Relay 2.
2. While still in the Program Switch screen for the North Switch, set Button 9 to ON
MODE for Relay 1
only
. Program Button 10 to OFF MODE for Relay 1
only
.
3. Program Button 7 to ON MODE for a spare relay or empty relay position (Relay
X).
4. Now go to the North Switch “SETUP” screen and set the parameter “7 ON =” to
the option “BTS 1-6 < 9 – 14”. (See Table 1.1 for full details).
5. Now, for the South Switch, program Button 1 to ON MODE for Relay 1 and
Relay 2. Program Button 2 to OFF MODE for Relay 1 and Relay 2.
6. While still in the Program Switch screen for the South Switch, set Button 9 to ON
MODE for Relay 2
only
. Program Button 10 to OFF MODE for Relay 2
only
.
7. Program Button 7 to ON MODE for the same spare or empty relay position you
used in step 3 above (Relay X).
8. Now go to the South Switch “SETUP” screen and set the parameter “7 ON =” to
the option “BTS 1-6 < 9 – 14”. (See Table 1.1 for full details).
9. Set another switch button, or a Digilink with an input coming from a partition
sensor, to turn ON Relay X when the partition is CLOSED and turn OFF Relay X
when the partition is OPEN.
10. That’s it. When the partition is closed or separate switch button is pressed, each
switch will only control the lights in their half of the room. When the partition is
open, each switch controls ALL of the lights in the room.
- 18 -
102