Guide for changing SIM card & phone number on 

existing system:

1. 

Disconnect power

2. 

Change the SIM card. See Figure 1.

3. 

Connect USB cable to the modem. See Figure 2

4. 

Download software from www.Actulux.dk/Techn. Info/Software

5. 

Power up system

6. 

Wait for 10 seconds

7. 

Run ConfigureModem.exe – Select COM port and enter phone 

 

number -> Press then Phone Setup. See figure 6

8. 

Disconnect USB cable

9. 

Disconnect modem power

10. 

Reconnect modem power

 
  

Remember to verify that the system is up and running after using the                      

  Actulux GSM Modem PC software. To do this, follow the steps in the 

 “Testing the system” section of this document, page 3.

Figure 6

EN

EN

Page 3/5

Page 4/5

Testing the system: 

(Make sure that this test will not trigger an alarm to the rest of the system)

The system sends a SMS with the following text in these cases:

1. 

Power up – ”Smoke Vent Monitor powered up”

2. 

Disconnect 230VAC – “MESSAGE FROM SMOKE VENT –  

 

SYSTEM NEEDS ATTENTION!”

3. 

Reconnect 230VAC – “MESSAGE FROM SMOKE VENT – 

 

SYSTEM OK”

4. 

Fire switch pressed – “MESSAGE FROM SMOKE VENT –

 

SYSTEM NEEDS ATTENTION”

5. 

Fire alarm reset – “MESSAGE FROM SMOKE VENT – OK”

 

 

   Be aware that the system will only send one SMS in the event of an alarm 

   or fail. If fail occurs before the alarm, then the user will only receive one 

   SMS and in this case it will be the “fail message” SMS.

Control of mobile network connection:

Since the modem uses external mobile network operators, we recommend 

checking the mobile connection regularly, by forcing the system into failure 

mode.

    

Содержание Gemalto 111950

Страница 1: ...Quick Guide GSM Modem for Control Panels 211725 Rev 0 3 21 09 2017 Actulux A S Haandvaerkervej 2 DK 9560 Hadsund Tel 45 98 57 40 90 info actulux com www actulux com ...

Страница 2: ... and terminal 30 for 24V supply 4 Ensure sustained power to modem in case of main power fail a At SVM control panel Jumper on J11 mounted See Figure 3 b At SV control panel F9 Fuse is connected between 24V Batt Sup See Figure 4 5 Connect alarm and fail relay s See Figure 5 6 Attach the modem to the mounting plate again IMPORTANT FOLLOW THE ORDER OF STEPS System setup 1 Download software from www A...

Страница 3: ...ge 3 5 Page 4 5 Testing the system Make sure that this test will not trigger an alarm to the rest of the system The system sends a SMS with the following text in these cases 1 Power up Smoke Vent Monitor powered up 2 Disconnect 230VAC MESSAGE FROM SMOKE VENT SYSTEM NEEDS ATTENTION 3 Reconnect 230VAC MESSAGE FROM SMOKE VENT SYSTEM OK 4 Fire switch pressed MESSAGE FROM SMOKE VENT SYSTEM NEEDS ATTENT...

Страница 4: ... Actulux A S Håndværkervej 2 DK 9560 Hadsund Denmark Tel 45 98 57 40 90 Fax 45 96 15 28 00 e mail info actulux com www actulux com EN EN Features Power 12V to 30VDC 300mA at 24V Dimensions HxWxD 180x110x60 mm Weight 0 6 kg Protection class IP65 Operating temperature 10 to 45 C CE marking in accordance with the EMC directive and low voltage directive Connection of unit has to be carried out by prof...

Отзывы: