Figure 1: Where and how to insert the SIM card

           

     

Figure 2: Where to insert the  

 

 

 

 

 

USB cable for configuration 

Electrical connection

 

                                

      

 

    

Figure 3: SVM control panel           

Figure 4: SV control panel  

power 

settings 

   power 

settings

   

Figure 5: Connection diagram between control panels and modem.

Box content:  ● GSM Modem

  

 

● USB-cable

 

  

Step by step guide:

 

Installation

1. 

Dismount the modem from the mounting plate before 

installation. (2 screws)

2. 

Insert SIM card into modem. See Figure 1

3. 

Connect power cable but 

do not power up yet –> +24V to terminal 1  

 

 

and GND to terminal 2

 

a. 

If SVM control panel is used, then use terminal 22 for GND  

 

 

 

and terminal 23 for 24V supply.

 

b. 

If SV control panel is used, then use terminal 29 for GND and   

 

 

terminal 30 for 24V supply.

4. 

Ensure sustained power to modem in case of main power fail.

 

a. 

At SVM control panel – Jumper on J11 mounted. 

 

 

See Figure 3. 

 

b. 

At SV control panel - F9 (Fuse) is connected between

 

 

 

24V & Batt Sup. See Figure 4.

5. 

Connect alarm- and fail relay’s. See Figure 5.

 

6. 

Attach the modem to the mounting plate again.

 

IMPORTANT! FOLLOW THE ORDER OF STEPS
System setup

1. 

Download software from www.Actulux.dk see Techn. Info

2. 

Open the folder and install the file: setup.exe

3. 

Connect the USB cable to the modem. See Figure 2.

4. 

Power up system

5. 

Wait 10 seconds

6. 

Run ConfigureModem.exe file – Select COM port and enter the

 

 

phone number -

> Press then Phone Setup.

7. 

Disconnect USB cable

8. 

Disconnect modem power

Set system in normal operation

1. 

Reconnect modem power

System is now running. The user will receive a SMS with the text:  

”Smoke Vent Monitor powered up!”

EN

EN

Page 1/5

Page 2/5

GSM MODEM

Содержание Gemalto 111950

Страница 1: ...Quick Guide GSM Modem for Control Panels 211725 Rev 0 3 21 09 2017 Actulux A S Haandvaerkervej 2 DK 9560 Hadsund Tel 45 98 57 40 90 info actulux com www actulux com ...

Страница 2: ... and terminal 30 for 24V supply 4 Ensure sustained power to modem in case of main power fail a At SVM control panel Jumper on J11 mounted See Figure 3 b At SV control panel F9 Fuse is connected between 24V Batt Sup See Figure 4 5 Connect alarm and fail relay s See Figure 5 6 Attach the modem to the mounting plate again IMPORTANT FOLLOW THE ORDER OF STEPS System setup 1 Download software from www A...

Страница 3: ...ge 3 5 Page 4 5 Testing the system Make sure that this test will not trigger an alarm to the rest of the system The system sends a SMS with the following text in these cases 1 Power up Smoke Vent Monitor powered up 2 Disconnect 230VAC MESSAGE FROM SMOKE VENT SYSTEM NEEDS ATTENTION 3 Reconnect 230VAC MESSAGE FROM SMOKE VENT SYSTEM OK 4 Fire switch pressed MESSAGE FROM SMOKE VENT SYSTEM NEEDS ATTENT...

Страница 4: ... Actulux A S Håndværkervej 2 DK 9560 Hadsund Denmark Tel 45 98 57 40 90 Fax 45 96 15 28 00 e mail info actulux com www actulux com EN EN Features Power 12V to 30VDC 300mA at 24V Dimensions HxWxD 180x110x60 mm Weight 0 6 kg Protection class IP65 Operating temperature 10 to 45 C CE marking in accordance with the EMC directive and low voltage directive Connection of unit has to be carried out by prof...

Отзывы: