Страница 1: ...Quick Guide GSM Modem for Control Panels 211725 Rev 0 3 21 09 2017 Actulux A S Haandvaerkervej 2 DK 9560 Hadsund Tel 45 98 57 40 90 info actulux com www actulux com ...

Страница 2: ... and terminal 30 for 24V supply 4 Ensure sustained power to modem in case of main power fail a At SVM control panel Jumper on J11 mounted See Figure 3 b At SV control panel F9 Fuse is connected between 24V Batt Sup See Figure 4 5 Connect alarm and fail relay s See Figure 5 6 Attach the modem to the mounting plate again IMPORTANT FOLLOW THE ORDER OF STEPS System setup 1 Download software from www A...

Страница 3: ...ge 3 5 Page 4 5 Testing the system Make sure that this test will not trigger an alarm to the rest of the system The system sends a SMS with the following text in these cases 1 Power up Smoke Vent Monitor powered up 2 Disconnect 230VAC MESSAGE FROM SMOKE VENT SYSTEM NEEDS ATTENTION 3 Reconnect 230VAC MESSAGE FROM SMOKE VENT SYSTEM OK 4 Fire switch pressed MESSAGE FROM SMOKE VENT SYSTEM NEEDS ATTENT...

Страница 4: ... Actulux A S Håndværkervej 2 DK 9560 Hadsund Denmark Tel 45 98 57 40 90 Fax 45 96 15 28 00 e mail info actulux com www actulux com EN EN Features Power 12V to 30VDC 300mA at 24V Dimensions HxWxD 180x110x60 mm Weight 0 6 kg Protection class IP65 Operating temperature 10 to 45 C CE marking in accordance with the EMC directive and low voltage directive Connection of unit has to be carried out by prof...