Installation and Commissioning Guide
Package Commercial Unit
39
Installation and Commissioning Guide - Package Commercial Unit
Doc. Part No. 0525-055 Ver. 9 220308
17.12. PCG340L/R
FAN PERFORMANCE DATA
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
% PWM
W
1450
50
550
54
692
58
837
62
978
67
1144
75
1328
1500
53
599
57
754
61
887
65
1044
70
1196
78
1380
1550
55
660
59
793
64
948
68
1104
73
1262
80
1431
1600
58
715
62
855
67
1005
71
1168
75
1306
84
1497
1650
61
765
65
909
70
1065
74
1225
79
1389
90
1570
1700
65
824
68
976
73
1128
77
1290
82
1469
95
1631
1720
66
849
69
997
74
1151
79
1320
83
1486
1750
68
892
72
1040
76
1190
81
1361
86
1542
1800
71
950
74
1096
79
1261
84
1438
90
1619
MOTOR /
BLOWER LIMIT
1850
74
998
78
1154
82
1328
88
1516
94
1712
1900
77
1052
81
1236
86
1417
92
1608
NOTES:
Performance Fan Curve shown is at Dry Coil Condition. Airflow
should be reduce with respect to the moisture content in the
air. All data provided does not include filters. Please review filter
manufacturer for application. 2.5 m/s face velocity point will
occur at 2156 l/s.
NOTES:
W
= Indoor Fan Power, Watts
PWM
= Pulse Width Modulation Setting, % PWM
(Adjustable through CPI3-2 Board located in electrical panel).
Factory PWM Setting = 69 % PWM for 100 Pa.
- Data in the box indicates Factory Default Setting.
JUMPER PIN
POSITION
INDOOR FAN
A
SCG400E
PCG400U/V/L/R
B
PCG340U/V/L/R
C
PCG330U/V/L/R
D
PCG300L/R
PKA300T-L/R
E
SCG290E
PCG290U/V/L/R
F
SRG260E
PCG260U/V
(CPI3-1) COMMERCIAL PWM INTERFACE BOARD
NOTES:
LED will show PWM without %.
Example: 69% PWM = 69 in LED.
LED adjustments are in 1 digit increments.
CPI 3
23787-3
C3
DISP2 DISP1
MODEL
A
B
C
D
E
F
ADJUST
V2
C2
P3
C1
+
+
P1
P2
V1.0
U4
U3
R11
R12
R13
R14
R15
C5
D3
R3
R4
C7
R2
R1
RV1
TRA-0100-R
D1
D2
P5
TX1
240VAC OUT
INPUT
R10
C8
P6
GND
0 - 10
V
PWM1 OUT
PWM2 OUT
P4
DAMAGE DUE TO
INCORRECT WIRING
VOIDS WARRANTY
CPI3-
1
S/No:
11G1
2276
IF
ON/OFF
IF
PWR
240VAC IN
ActronAir
LED FAN
PWM
DISPLAY
JUMPER PIN
SET AS PER
TABLE BELOW
PWM
ADJUSTMENT
(POTENTIOMETER)
0
50
100
150
200
250
300
350
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
Airflow
50
150
250
350
100
200
300
0
1450
1600
1750
1500
1650
1800
1900
1550
1700 1720
1850
55% PWM
50% PWM
95% PWM
MOTOR / BLOWER LIMIT
60% PWM
69% PWM
70% PWM
75% PWM
80% PWM
85% PWM
90% PWM
EXTERNAL S
TA
TIC PRE
SSURE (P
a)
APPLICATION RANGE
AIRFLOW (l/s)
Nominal Airflow = 1720 l/s
65% PWM
Содержание PCA300U Series
Страница 53: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...
Страница 54: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...
Страница 55: ...THIS PAGE WAS INTENTIONALLY LEFT BLANK ...