24
Operation Manual
LC7-2 Wall Control
Operation Manual - LC7-2 Wall Control
Document: 0525-080
Ver. 1 190923
13.03. Temperature Set Back
Normally, the air conditioning system is turned off at unoccupied times or at night, which can result in the building
temperature becoming quite hot (e.g. 30
o
C) or quite cold (e.g. 12
o
C). When you Turn-ON the air conditioning
system, it can take a long time to achieve a comfortable temperature (e.g. 23
o
C). The temperature set back feature
will maintain the building temperature at a pre-determined and reasonable temperature closer to your chosen set
temperature (e.g. 23
o
C), thus giving you a big head start in achieving your comfortable temperature.
The system must be
Turned Off
before performing these procedures.
13.03.01. Activating the Temperature Set Back
NOTE
Activating Temperature Set back may cause unit to operate even if the LC7-2 Wall control is Off. Please proceed
with activating the Temperature Set back feature if you understand the purpose and operating parameters. For
further enquires, please contact ActronAir Technical Support on 1800 119 229.
1. Press the
PROG
button to enter program Menu.
2. Press the
or
buttons to navigate to Program Menu
03
. .
3. Press the
PROG
button to enter Program Menu
03
. Display will show
SET BACK
indicator and
OFF
field is
blinking.