CHANGING THE UV BULB

2.  Remove the cover by lifting away 

from the base.

3.  Remove the UV bulb by lifting the end 

away from the bulb retaining clamp.

1.   Remove the four (4) cover screws from the 

sides of the INDUCT 500.

4.  Unplug the UV bulb from the 

power supply.

5.  Replace the UV bulb by 

reversing steps 3 and 4.

6.  Return cover and 

replace screws.

WARNING:

 Disconnect Power from the INDUCT 

500 before servicing.

PARTS VIEW

CLEANING/MAINTENANCE

1.   Disconnect the power supply to the INDUCT 500 

and the PTAC unit.

2.  Remove the INDUCT 500 from PTAC the unit.

3.   Wipe the cover of the INDUCT 500 with a  

damp cloth.

4.   Use a vacuum with a hose attachment to vacuum 

dust from the ActivePure Matrix (honeycomb) on either 
side of the INDUCT 500.

5.  When the INDUCT 500 cover is free from 

moisture, reposition in the PTAC and plug power 
supply back into outlet.

UV Bulb  

9950201 (Ozone Free)

9950202 (Ozone)

Power Supply

49873 (US)

49874 (Euro)

WARNING:

 UV Light in operation. Disconnect unit 

from power supply before servicing. Failure to follow 
warnings may result in severe eye damage and 
electrical shock.

NOTE:

 We recommend changing the UV bulb in the INDUCT 

500 once a year, if cycled with fan on/off, and every 2 years, for 
continuous operation. If the INDUCT 500 unit is connected to the fan 
circuit, it will only operate when the fan runs. The INDUCT 500 unit 
can operate continuously if it is connected separately from the fan. 

NOTE:

 It is recommended to vacuum the ActivePure Matrix 

(honeycomb) surface monthly.