CHANGING THE UV BULB
2. Remove the cover by lifting away
from the base.
3. Remove the UV bulb by lifting the end
away from the bulb retaining clamp.
1. Remove the four (4) cover screws from the
sides of the INDUCT 500.
4. Unplug the UV bulb from the
power supply.
5. Replace the UV bulb by
reversing steps 3 and 4.
6. Return cover and
replace screws.
WARNING:
Disconnect Power from the INDUCT
500 before servicing.
PARTS VIEW
CLEANING/MAINTENANCE
1. Disconnect the power supply to the INDUCT 500
and the PTAC unit.
2. Remove the INDUCT 500 from PTAC the unit.
3. Wipe the cover of the INDUCT 500 with a
damp cloth.
4. Use a vacuum with a hose attachment to vacuum
dust from the ActivePure Matrix (honeycomb) on either
side of the INDUCT 500.
5. When the INDUCT 500 cover is free from
moisture, reposition in the PTAC and plug power
supply back into outlet.
UV Bulb
9950201 (Ozone Free)
9950202 (Ozone)
Power Supply
49873 (US)
49874 (Euro)
WARNING:
UV Light in operation. Disconnect unit
from power supply before servicing. Failure to follow
warnings may result in severe eye damage and
electrical shock.
NOTE:
We recommend changing the UV bulb in the INDUCT
500 once a year, if cycled with fan on/off, and every 2 years, for
continuous operation. If the INDUCT 500 unit is connected to the fan
circuit, it will only operate when the fan runs. The INDUCT 500 unit
can operate continuously if it is connected separately from the fan.
NOTE:
It is recommended to vacuum the ActivePure Matrix
(honeycomb) surface monthly.