ACT ACT-VCC-5000 Скачать руководство пользователя страница 14

Rev A 

 

ACT-VCC-5000-AC) 

 

  

 

 

 

 

14 

 

Figure 6.2 LED Display faceplate 

 

 

Table 6.2 Definition of the symbols 

 

Indicator Icon 

Definition 

Is lit 

Is blinking 

 

Parameter setting 

Under setting status 

Self-test status 

 

*Heating status 

*Heater is running 

*Heater has failed when 

off    

 

Cooling 

Compressor is running 

Compressor has failed when 

off 

 

External fan 

External fan is running 

External fan has failed when 

off   

 

 

 

--- 

--- 

--- 

 

Alarm / Warning 

Alarm / Warning 

--- 

*Not all options are available for all units 

 

Setting Display Parameters:

 

Press the "M" key for 5 seconds, causing the system to enter into parameter setting mode. The display will show 

the “Pxx” code.   

 

Use arrow "



" keys to choose the desired item.   

 

Press the "S" button to select. The display will show the selected item’s current parameter values; use 

arrow "



" keys to adjust the value and press the "S” button to lock in that value.   

o

  At this time, a four-digit password input interface will be shown as “0000”; please key in the 

customer default password

 “1234” 

and use the "S" key to confirm each digit. Once the correct 

password is entered, the system will save the new parameter value and display code “End”, then 

return to normal display status automatically.   

Note:

   

 

While in the parameter setting mode, press the "M" key to exit..   

 

If no key is touched within 30 seconds, the system will return to normal mode automatically.   

Содержание ACT-VCC-5000

Страница 1: ...ACT VCC 5000 AC Cabinet Air Conditioner User Manual Read this manual carefully before installation and use...

Страница 2: ...s 4 2 3 Working Principles 4 2 4 Product features 4 2 5 Technical Specifications 5 2 6 Air Circulation and Remote Mounting 5 2 7 Operation of the Unit 6 2 8 Condensate Handling 6 2 9 LED Display Param...

Страница 3: ...e cooling device intended for applications where the internal air of a sealed electrical enclosure must be cooled or maintained at a particular temperature This manual will provide an overview of the...

Страница 4: ...ressure vapor travels through a condenser where it dissipates heat to the environment The high pressure condensate then flows through an expansion valve which reduces the fluid s pressure and partiall...

Страница 5: ...plications If the unit is to be mounted remotely to cool an enclosure ductwork and a separting plate must be used as shown in Figure 2 3 Ductwork should be made as short as possible to minimize the im...

Страница 6: ...its lowest speed o Active Cooling mode If the air temperature is greater than the setpoint temperature the unit will run on normal cooling mode to achieve the setpoint temperature o Heating mode Optio...

Страница 7: ...12 hours 0 72 hours P97 Return to factory setting Pressing the S key will return the product to default factory settings Heating functions are optional and not included on all units The above paramete...

Страница 8: ...ervoltage warning E10 AC Power undervoltage warning E11 Refrigerant circuit pressure is too high warning E12 Refrigerant circuit pressure is too low warning E13 Heater current overload warning E14 Hea...

Страница 9: ...ing straps are unbroken and that the wooden box is undamaged not deformed or wet Use scissors or a knife to dismantle the packing belt then open the wooden box After opening the package please check t...

Страница 10: ...ed gasket Do not turn the unit on immediately after finishing the installation the unit must remain standing vertically for more than 30 minutes before being turned on to allow the compressor oil to d...

Страница 11: ...e All wires must be properly torqued to the relevant terminals All national wiring regulations and local electrical codes should be followed based upon instalation location Safety Reminder notes befor...

Страница 12: ...e IN N Line L Line Lighting Arrester CTRL NO COM NC T R T R INT Temp Sensor Cond Temp Sensor Inter Fan Exter Fan1 R S C Compressor 4 F 1 4 F 2 8 F J7 J8 J6 J32 J28 Evap Temp Sensor L Line J31 J30 rela...

Страница 13: ...wer supply voltage is normal and consistent with the requirements on the nameplate 6 2 Operating the Unit Apply power to the unit The product will first run a self test program and then the unit will...

Страница 14: ...arameter setting mode The display will show the Pxx code Use arrow keys to choose the desired item Press the S button to select The display will show the selected item s current parameter values use a...

Страница 15: ...the cable if damaged 2 Voltage Stability Use the multimeter to measure the Air Conditioner input voltage in order to gauge whether the voltage is within normal range If the voltage is not within the n...

Страница 16: ...larm stops Supply voltage overload The compressor current is not within the normal range Turn off the power supply immediately Use a multimeter to measure the voltage do not power on the switch until...

Страница 17: ...ve inspection test acceptance and use Seller s warranty shall run to Buyer its successors assigns and customers and users of products sold by Buyer Seller agrees to replace or correct defects of any G...

Страница 18: ...Rev A ACT VCC 5000 AC 18 IDEAL APPLICATIONS Questions or Comments ACT Quality Department quality 1 act com or call 717 295 6061 to reach the Sales staff for assistance on custom orders...